Main Categories

Contact: [email protected] (Mark McEwen)
Origin: CSA
Close date: Aug 18, 2026
View moreView less
 

Draft Amendment to C22.1

Categories: Electrical
Contact: [email protected] (Adam Lawrence)
Origin: CSA
Close date: Aug 22, 2026
View moreView less
 

1.1 

This Standard applies to deadfront indoor enclosed and outdoor enclosed assemblies of switchgear devices such as

a)    switches;

b)   interrupting devices;

c)    circuit breakers as defined in Clause 3; and

d)   control, metering, protective, and regulating equipment with associated interconnections and supporting structures.

1.2 

This Standard covers equipment with a nominal voltage of 46 kV or less that is intended to be used

a)    in accordance with the Canadian Electrical Code, Part I;

b)   in non-hazardous locations;

c)    for controlling and protecting the power from generators or other sources; and

d)   for supplying electrical energy to power and lighting circuits.

1.3 

This Standard does not apply to

a)    switchboards for power distribution (see CSA C22.2 No. 244);

b)   switchboards for communication circuits;

c)    panelboards (see CSA C22.2 No. 29);

d)   industrial control equipment (see CSA C22.2 No. 14);

e)    low-voltage assemblies consisting of separately supported enclosed switches;

f)    enclosed circuit breakers (see CSA C22.2 No. 5);

g)    service meters with interconnection between them enclosed in raceways;

h)   individual low-voltage switchgear and controlgear switching devices such as contactors or proximity switches (see CSA C22.2 No. 60947 series and Note 2 below); and

i)     switchgear assemblies relying solely on solid dielectric material as primary insulation (see CSA C22.2 No. 297)

Notes:

1)    Manufacturers and installers of switchgear assemblies approved under this Standard should take due note of the Canadian Electrical Code, Part I, with respect to the location of switchgear devices in areas where certain components might not be acceptable.

2)    The terms “switchgear” and “switchgear assemblies” used within the content of this Standard refer to assemblies primarily intended to provide protection and control of either low- or high-voltage feeder and sub-feeder circuits in connection with the generation, transmission, distribution, and conversion of electric power. These terms should not be confused with the IEC terms “switchgear” and “controlgear” used within the context of the CSA C22.2 No. 60947 series of standards which cover individual or combinations of individual low-voltage switching devices intended for the control, measurement, or regulation of energy-consuming equipment.

1.4 

Clauses 2 to 6 apply to all switchgear assemblies and are supplemented and amended by

a)    Clause 7 for low-voltage switchgear assemblies; and

b)   Clause 8 for high-voltage switchgear assemblies.

Note: See Annex F for additional requirements applicable for pressurized gas insulated switchgear.

1.5 

In this Standard, “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the standard; “should” is used to express a recommendation or that which is advised but not required; and “may” is used to express an option or that which is permissible within the limits of the standard.

Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material.

Notes to tables and figures are considered part of the table or figure and may be written as requirements.

Annexes are designated normative (mandatory) or informative (nonmandatory) to define their application.

Contact: [email protected] (Mark McEwen)
Origin: CSA
Close date: Aug 22, 2026
View moreView less
 

Draft Amendment to C22.1

Categories: Electrical
Contact: [email protected] (Claudia Hamza)
Origin: CSA
Close date: Aug 23, 2026
View moreView less
 

1.1 

This Standard applies to electric signs, outline lighting, and display equipment for indoor or outdoor use, in nonhazardous locations, intended for installation in accordance with the Canadian Electrical Code, Part I wherein the sources of light are light emitting diodes (LED) or other electric lamp types including high voltage luminous-discharge types.

1.2

Electric signs using high voltage luminous-discharge-tubes are intended for installation on branch circuits of not more than

a)   750 V between conductors and involving lamp voltages of not more than 15 000 V for stationary signs; and

b)   125 V between conductors and involving lamp voltages of not more than 7500 V for portable signs.

c)   750 V between conductors and involving lamp voltages of more than 7500 V but not exceeding 15 000 V, not more than 7500 V to ground, and secondary current ratings not more than 30 mA, for portable and show-window luminous-discharge-tube signs and displays for indoor use.

1.3 

Electric signs covered by this Standard include sectional signs, trailer-mounted signs, canopy signs, recessed signs, pole mounted signs, changing message signs, mechanically or electrically animated signs, and digital-display signs.

1.4 

This Standard also applies to high voltage luminous-discharge-tube components (see Annex A), neon transformers and power supplies (see Annex B), and LED kits and LED retrofit kits for signs (see Annex C).

1.5 

These requirements do not cover:

a)   Luminaires, including those used for used for billboard illumination and other than advertising purposes (e.g., bathroom signage);

b)   Portable luminaires;

c)   Emergency lighting products;

d)   Signs that do not use electricity;

e)   The use of special-use lamps and LED arrays unless they are free of any photobiological hazards in accordance with CSA C22.2 No. 62471; and

f)    Field-assembled signs approved in accordance with SPE-1000.

1.6 

The values given in SI (metric) units are the standard. The values given in parentheses are for information only.

1.7 

In this Standard, “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the standard; “should” is used to express a recommendation or that which is advised but not required; and “may” is used to express an option or that which is permissible within the limits of the standard.

Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material.

Notes to tables and figures are considered part of the table or figure and may be written as

requirements.

Annexes are designated normative (mandatory) or informative (nonmandatory) to define their application.

Categories: Energy
Contact: [email protected] (Julie Cairns)
Origin: CSA
Close date: Aug 23, 2026
View moreView less
 

1.1 Inclusions

This Code applies to the design, location, construction, operation, operator training, and maintenance of

a) CNG vehicle refuelling stations; and

b) CNG bulk transport filling and decanting stations, including

i)     those that are fixed or mobile and intended for private or public dispensing operations; and

ii)    bulk transport filling and decanting stations that feed CNG pressure reduction stations or other non-vehicle uses.

1.2 Exclusions

This Code does not apply to

a)    refuelling vehicles with liquefied natural gas (LNG), which is covered by CSA B108.2. However, when an LNG facility has capacity for CNG vehicle refuelling from a liquid to compressed natural gas system (L/CNG system), this Code applies to facilities downstream of the L/CNG system odourizer’s outlet isolation valve;

b)    transfer of CNG from the CNG vehicle fuel storage system of one vehicle to the CNG vehicle fuel storage system of another vehicle;

c)    certified refuelling appliances (RFAs), except where

i)     the total flow capacity of a single refuelling appliance (RA), or multiple refuelling appliances is greater than 0.850 Sm3/min (30 SCFM); or

ii)    the RA is connected to piping tubing or storage. In this case, this Code applies to the piping, storage and dispensing system, starting at the outlet of the individual RA (see Figure D.1); and

d)    mobile equipment containing compressed natural gas in accordance with Transport Canada’s Transportation of Dangerous Goods Act and Regulations.

1.3 Pressure terminology

Unless otherwise specified, all references to pressure throughout this Code are to be considered gauge pressures.

1.4 Terminology

In this Code, “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the Code; “should” is used to express a recommendation or that which is advised but not required; and “may” is used to express an option or that which is permissible within the limits of the Code.

Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material.

Notes to tables and figures are considered part of the table or figure and may be written as requirements.

Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.

1.5 Use of SI units

The values given in SI units are the units of record for the purposes of this Code. The values given in parentheses are for information and comparison only.

Notes:

1)    IEEE/ASTM SI 10 or ISO 80000-1 can be used as a guide when converting U.S. customary units to SI units.

2)    Where the abbreviation “gal” is used in this Code, it indicates a U.S. gallon equivalent to 3.785 L water capacity.

3)    This Code was originally developed using the U.S. customary system of measurement and subsequently converted to SI units having three significant digits. Every attempt has been made to provide accurate conversion values; however, when designing systems using these values, engineering judgment should be applied.

Categories: Energy
Contact: [email protected] (Julie Cairns)
Origin: CSA
Close date: Aug 23, 2026
View moreView less
 

1.1 Inclusions

This Code applies to

a)   the design, location, construction, operation, operator training, and maintenance of LNG refuelling stations;

b)   LNG mobile refuelling units (MRUL) or LNG portable refuelling units (PRUL) with single containment storage tanks up to 265 m3 (70 000 gal) water capacity employed for vehicle LNG dispensing operations;

c)   shop-fabricated and assembled refuelling stations when used to receive and store LNG to dispense LNG into vehicle fuel tanks; and

d)   the LNG portion of stations that vapourize and pressurize LNG to obtain CNG, up to and including the odourizer’s outlet isolation valve.

Note: When a refuelling station dispenses fuels in addition to LNG, this Code applies only to the LNG refuelling system and equipment.

1.2 Exclusions

This Code does not apply to

a)   indoor refuelling;

b)   marine vessel LNG fuelling facilities;

c)   rail locomotive LNG fuelling facilities;

d)   equipment, piping, or tubing downstream of the L/CNG system odourizer’s outlet isolation valve (see CSA B108.1);

e)   CNG equipment including storage, compression, and/or dispensing equipment;

f)    CNG mobile refuelling units (MRUG) or CNG portable refuelling units (PRUG);

g)   equipment, piping, or tubing downstream of the gas pressure regulator for closed boil-off gas systems;

h)   dispensing of LNG other than into vehicle or cargo fuel tanks;

i)     liquefaction equipment;

j)     LNG engine fuel systems;

k)   LNG and CNG repair garages;

l)     underground piping or tubing for LNG;

m)  LNG storage tanks, pumps, and process piping or tubing when an LNG refuelling station is sharing the LNG plant storage tank; and

n)   transfer of LNG from the LNG vehicle fuel storage system of one vehicle to the LNG vehicle fuel storage system of another vehicle.

Note: This does not apply to a bulk fuel storage system.

1.3 Pressure terminology

Unless otherwise specified, all references to pressure throughout this Code are to be considered gauge pressures.

1.4 Terminology

In this Code, “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the Code; “should” is used to express a recommendation or that which is advised but not required; and “may” is used to express an option or that which is permissible within the limits of the Code.

Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material.

Notes to tables and figures are considered part of the table or figure and may be written as requirements.

Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.

1.5 Units of measurement

The values given in SI units are the units of record for the purposes of this Code. The values given in parentheses are for information and comparison only.

Notes:

1)   IEEE/ASTM SI 10 or ISO 80000-1 can be used as a guide when converting U.S. customary units to SI units.

2)   Where the abbreviation “gal” is used in this Code, it indicates a U.S. gallon equivalent to 3.785 L water capacity.

3)   This Code was developed originally using the U.S. customary system of measurement and subsequently converted to SI units having three significant digits. Every attempt has been made to provide accurate conversion values; however, when designing systems using these values, engineering judgment should be applied.

Categories: Electrical
Contact: [email protected] (Clara Yeung)
Origin: CSA
Close date: Aug 23, 2026
View moreView less
 

1.1 

This Standard applies to rigid PVC conduit — type EB1 for encasement in concrete or masonry and type DB2/ES2 for direct burial or encasement in concrete or masonry — and associated fittings in accordance with the Rules of the Canadian Electrical Code, Part I, for ordinary locations.

1.2 

The conduits and associated fittings covered by this Standard are intended for a maximum continuous operating temperature of 75 °C.

1.3 

The accessories covered by this Standard include straight couplings, 5° angle couplings, caps, plugs, bell end terminators, bends, and adapters.

1.4 

In CSA Standards, “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the standard; “should” is used to express a recommendation or that which is advised but not required; “may” is used to express an option or that which is permissible within the limits of the standard; and “can” is used to express possibility or capability. Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material. Notes to tables and figures are considered part of the table or figure and may be written as requirements. Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.

Categories: Energy
Origin: CSA
Close date: Aug 25, 2026
View moreView less
 

1.1  Purpose

This Standard establishes requirements for pressure-retaining systems, components, and their supports over the service life of a CANDU NPP. The requirements of this Standard address

construction activities; and

in-service inspection, modification, repair, and replacement activities.

1.2  Applicability to pressure-retaining systems

This Standard applies to all pressure-retaining systems, including their components and supports, in a CANDU NPP.

1.3  Applicability to containment components

This Standard applies to containment components, but does not apply to containment structures which are covered in the CSA N287 Series of Standards.

1.4  Exclusion of portable assemblies

This Standard does not apply to portable assemblies of pressurized items that are temporarily connected to a system or component to enable testing, venting, draining, calibration, or other maintenance activities, provided that they

do not reduce the ability of a system to perform its design safety function;

are under surveillance when connected and are removed upon completion of their function; and

are constructed to Standards deemed by the licensee to be suitable for the application.

Note: Safety analysis, environmental qualification programs, or seismic qualification may be used to satisfy the conditions in this Clause.

 

1.5  Exclusion of sensing elements

This standard does not apply to sensing elements of instruments, except when the sensing element is included in the design of a component pressure boundary.

 

1.6  Terminology

In this Standard, “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the Standard; “should” is used to express a recommendation or that which is advised but not required; and “may” is used to express an option or that which is permissible within the limits of the Standard.

Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material.

Notes to tables and figures are considered part of the table or figure and may be written as requirements.

Annexes are designated normative (mandatory) or informative (nonmandatory) to define their application.

1.7  Units of measurement

The values given in SI units are the units of record for the purposes of this Standard. The values given in parentheses are for information and comparison only. The units in this Standard may be converted in accordance with the ASME BPVC, Section III, NCA-1150.

Categories: Energy
Origin: CSA
Close date: Aug 25, 2026
View moreView less
 

1.1  Objet

La présente norme définit les exigences en matière de systèmes et de composants sous pression ainsi que leurs supports pendant la durée en service dans une centrale nucléaire CANDU. Les exigences de la présente norme traitent de ce qui suit :

les activités de construction; et

les activités d’inspection en service, de modification, de réparation et de remplacement.

1.2  Applicabilité aux systèmes sous pression

Cette norme s'applique à tous les systèmes sous pression, y compris leurs composants et supports d'une centrale nucléaire CANDU.

1.3  Applicabilité aux composants de confinement

La présente norme vise les composants de confinement, mais non les enceintes de confinement qui sont elles-mêmes visées par la série de normes CSA N287.

1.4  Exclusion des ensembles portatifs

La présente norme ne s'applique pas aux ensembles portatifs constitués d'articles sous pression accouplés temporairement à un système ou composant afin de permettre la mise à l'essai, l'évacuation, la vidange, l'étalonnage ou autre activité d'entretien, dans la mesure où :

ils ne réduisent pas la capacité d'un système à remplir sa fonction de sûreté de conception;

ils sont surveillés pendant qu'ils sont accouplés et ils sont retirés une fois la tâche accomplie; et

ils sont construits selon des normes jugées acceptables par le titulaire de permis en regard de l'application visée.

Note : Des analyses de sûreté, des programmes de qualification en environnement ou la qualification sismique peuvent être utilisés pour satisfaire à cet article.

 

1.5  Exclusion des éléments de détection

Cette norme ne s’applique pas aux éléments de détection des instruments, sauf lorsque l’élément de détection est inclus dans la conception de l’enveloppe sous pression d’un composant.

 

1.6  Terminologie

Dans la présente norme, le terme « doit » indique une exigence, c.-à-d. une prescription que l’utilisateur est obligé de respecter pour assurer la conformité à la présente norme; « devrait » indique une recommandation ou ce qu’il est conseillé, mais non obligatoire; et « peut » indique une option ou ce qui est permis compte tenu des limites de la présente norme.

Les notes qui accompagnent les articles ne comprennent pas d'exigences ni d'exigences alternatives; le but d'une note accompagnant un article est de séparer du texte les éléments explicatifs ou informatifs.

Les notes au bas des tableaux et des figures font partie du tableau ou de la figure et peuvent être rédigées comme des exigences.

Les annexes sont qualifiées de normatives (obligatoires) ou d'informatives (facultatives) pour en préciser l'application.

1.7  Unités de mesure

Les valeurs indiquées en unités SI sont les valeurs officielles dans la présente norme. Les valeurs entre parenthèses sont données à titre d’information et pour fin de comparaison seulement. Les unités dans cette norme peuvent être converties conformément à la section III du BPVC de l'ASME, NCA-1150.

Categories: Electrical
Contact: [email protected] (Claudia Hamza)
Origin: CSA
Close date: Aug 28, 2026
View moreView less
 

1.1 These requirements cover permanently installed devices, hereafter referred to as dimmers, that employ a dimming function intended for control of lighting loads of the magnetic ballast, transformer, electronic ballast, self-ballasted lamp, tungsten-filament type, or light-emitting-diode (LED), and are intended to be installed in a wallbox or are provided with an enclosure for flush or surface mounting in accordance with the Canadian Electrical Code, Part I (CE Code), and the National Electrical Code (NEC), NFPA 70.


1.2 These requirements cover dimmers, other than touch dimmers, rated 600 volts ac or less, for installation on a 20-ampere or less branch circuit.


1.3 These requirements cover touch dimmers rated 120 volts ac or less for installation on a 20-ampere or less branch circuit.


1.4 These requirements cover dimmers, including touch dimmers, and electronic switches, having a minimum power rating of 300 watts incandescent or 300 volt-amperes in increments of 50 watts or 50 volt-amperes.


1.5 Devices may have additional current ratings based upon the additional lighting loads as specified by the manufacturer.


1.6 A device incorporating other functions (for example, speed control) in addition to a dimming function is evaluated on the basis of compliance with the applicable requirements for the dimming function in this Standard as well as requirements for the other functions in the applicable standards.


1.7 These requirements do not cover dimmers that use only a resistor or a transformer to perform the dimming function.


1.8 These requirements do not cover modular, cabinet or console type constructions.


1.9 These requirements do not cover dimmers intended primarily for use in theaters. Dimmers for use in theaters are covered by UL 508/CSA C22.2 No. 14.

 

Contact: [email protected] (Mark McEwen)
Origin: CSA
Close date: Aug 28, 2026
View moreView less
 

Draft Amendment to C22.1

Origin: CSA
Close date: Aug 29, 2026
View moreView less
 

1.1 General

This Standard provides a set of hydraulic testing specifications and performance metrics for temporary emergency flood protection barriers in Canadian environments by

defining standard terminology to use when describing floods and flood protection barriers;

detailing a set of hydraulic testing requirements for flood protection barriers (see exclusions in Clause 1.2);

outlining different environments for flood protection barrier use (i.e., environmental categories) and discussing the testing and performance requirements for these environments; and

providing technology developers and testing laboratories with a defined and consistent set of hydraulic testing conditions required for flood barrier deployment in Canadian environments.

Note: See also ANSI/FM 2510 and BSI Standards Publication Parts 1 and 2.

1.2 Exclusions

This Standard applies only to the hydraulic testing of temporarily deployed emergency flood protection barrier systems (i.e., those systems that are removed after flood events). Permanently affixed flood barriers fall outside of the scope of this Standard.

The Standard does not apply to initial planning, new development, new expansions and construction, or site closure/remediation.

This Standard does not apply to stormwater systems, which are covered in CSA W211.

Out-of-scope items are noted for awareness only, but organizations may choose to include those aspects to fit their scope needs. These out-of-scope items include but are not limited to

any types of testing of the flood protection barrier outside of hydraulic testing (e.g., strength of materials[KC1] [KC2] , UV exposure and degradation, foundation design);

any type of non-temporary or permanently affixed or installed flood protection barrier (e.g., walls, seawalls, dykes);

any testing of the barrier individual components (e.g., connection clamps, anchor bolts, materials testing);

any specifications around or testing of auxiliary equipment that supports flood protection barrier deployment (e.g., flood abatement pumps, backwater valves); and

any specifications around the manufacturing process of the flood protection barriers.

1.3 Terminology

In this Standard, “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the Standard; “should” is used to express a recommendation or that which is advised but not required; and “may” is used to express an option or that which is permissible within the limits of the Standard.

Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material.

Notes to tables and figures are considered part of the table or figure and may be written as requirements.

Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.

1.4 Units of measurement

The values given in SI units are the units of record for the purposes of this Standard. Dimensional lumber references refer to U.S. customary units as these products are commonly referred to within Canada by their trade name in those units.

Note: See Annex A.

 [KC1]Does Strength of Materials cover the reusing of temporary barriers, including fatigue metrics, lifespan of the barriers, or limits on how many times such barriers can be reused?

 [KC2]Not part of scope

Contact: [email protected] (Mark McEwen)
Origin: CSA
Close date: Aug 31, 2026
View moreView less
 

Draft Amendment to C22.1