Electrical
2 New Editions
1.CSA ISO/IEC 18031
2.CSA ISO/IEC 24759
6 New Standards
1.CSA ISO/IEC 14888-4
2.CSA ISO/IEC TS 24462
3. CSA ISO/IEC 27035-4
4. CSA ISO/IEC 27554
5. CSA ISO/IEC 27561
6. CSA ISO/IEC 19790
1 New Amendment
1. CSA ISO/IEC 27013:2021/AMD1:2024
1.1 General
This standard specifies the requirements for flexible cords, elevator cables, and hoistway cables rated 600 V maximum intended for use in accordance with CAN/CSA C22.1, Canadian Electrical Code, Part I, in Canada, NOM-001-SEDE, La Norma de Instalaciones Electricas, in Mexico, and NFPA 70, National Electrical Code (NEC), in the United States.
1.2 Products included
This standard covers the following products:
a) Service cords;
b) Elevator cables;
c) Hoistway cables;
d) Heater cords;
e) Range and dryer cords;
f) Tinsel and lamp cords;
g) Special use cords; and
h) Shore power cable.
1.3 National differences
In cases where product types are not approved in all three countries, a national difference is indicated by superscripts, as shown below:
Superscript letter National difference*
c For use in Canada only
m For use in Mexico only
u For use in United States only
c,m For use in Canada and Mexico only
c,u For use in Canada and United States only
m,u For use in Mexico and United States only
1.1
This Standard describes general requirements, apparatus, and test methods to be used in carrying out applicable tests and calculations for rigid nonmetallic conduits, elbows, bends, and associated fittings required by the rigid nonmetallic conduit Standards of the Canadian Electrical Code, Part II.
1.2
The various types of rigid nonmetallic conduits are as follows:
a) rigid PVC conduit for direct burial and for masonry and concrete encasement, as specified in CSA C22.2 No. 211.1; and
b) rigid PVC (unplasticized) conduit, as specified in CSA C22.2 No. 211.2.
1.1 This Part is intended to be read together with the Standard for Low-Voltage Fuses – Part 1: General Requirements, hereafter referred to as Part 1. The titles of the Clauses in this Part corresponds to the similarly titled Clauses in Part 1. The requirements of Part 1 apply unless modified by this Part. For the Part 1 requirements, refer to the Standard for Low-Voltage Fuses – Part 1: General Requirements, NMX-J-009/248/1-ANCE / CSA C22.2 No. 248.1 / UL 248-1.
1.2 This Standard applies to Class R fuses rated 600 A or less and either 250 or 600 V ac. DC ratings are optional.
This part of IEC/IEEE 62395-1 specifies requirements for electrical resistance trace heating systems and includes general test requirements.
This document pertains to trace heating systems that can comprise either factory-fabricated or field-assembled (work-site) units, and which can be series and parallel trace heaters or surface heaters (heater pads and heater panels) that have been assembled and/or terminated in accordance with the manufacturer’s instructions.
This document also includes requirements for termination assemblies and control methods used with trace heating systems.
This document provides the essential requirements and testing appropriate to electrical resistance trace heating equipment used in industrial and commercial applications. The products complying with this document are intended to be installed by persons who are suitably trained in the techniques required and that only trained personnel carry out especially critical work, such as the installation of connections and terminations. Installations are intended to be carried out under the supervision of a qualified person who has undergone supplementary training in electric trace heating systems.
This document does not include or provide for any applications in potentially explosive atmospheres.
This document does not cover induction, impedance or skin effect heating.
Trace heating systems are grouped into different types of applications and the different conditions found during and after installation necessitate different requirements for testing. Trace heating systems are usually for a specific type of installation or application. The product type grouping, applications and product attributes are indicated in Table 1.
NOTE Trace heating systems intended for use in explosive atmospheres are the subject of IEC/IEEE-60079-30-1 and IEC/IEEE- 60079-30-2.
1DV.1 Modification of Clause 1 to replace the first sentence of the third paragraph with the following:
This document provides the essential requirements and testing appropriate to electrical resistance trace heating equipment used in industrial, commercial, and residential applications.
1DV.2 (Canada only) Modification of Clause 1 by adding the following:
This document does not apply to space heating products covered by CSA C22.2 No. XXX.
1DV.3 (United States only) Modification of Clause 1 by adding the following:
This document does not apply to space heating products covered by UL 2683.
1DV.4 (Canada only) This Standard applies to the safety of such equipment designed and constructed for installation and use in accordance with CSA C22.1, Canadian Electrical Code, Part I.
1DV.5 (United States only) This Standard applies to the safety of such equipment designed and constructed for installation and use in accordance with NFPA 70. National Electrical Code (NEC).
This part of IEC/IEEE 62395 provides detailed recommendations for the system design, installation, maintenance and repair of electrical resistance trace heating systems in industrial and commercial applications. This document does not include or provide for any applications in potentially explosive atmospheres.
This document pertains to trace heating systems that can comprise either factory fabricated or field-assembled (work-site) units, and which can be series or parallel trace heaters, or surface heaters (heater pads or heater panels) that have been assembled and/or terminated in accordance with the manufacturer's instructions.
The products covered by this document are intended to be installed by persons who are suitably trained in the techniques required and that only trained personnel carry out especially critical work, such as the installation of connections and terminations. Installations are intended to be carried out under the supervision of a qualified person who has undergone supplementary training in electric trace heating systems.
This document does not cover induction, impedance or skin effect heating.
Trace heating systems and surface heating systems can be grouped into different types of installations. These are characterized by different requirements for testing and are usually certified for a specific type of installation or application. Typical applications for the different types of installation are shown in Table 1.
This clause of Part 1 is applicable, except as follows:
Addition:
This document applies to hand-held and walk-behind lawn trimmers and lawn edge trimmers, used by a standing operator for cutting grass, weeds or similar soft vegetation, and grass trimmers, brush cutters and brush saws used by a standing operator for cutting grass, weeds, brush, bushes, saplings and similar vegetation.
This document does not apply to
– hand-held machines having a mass of 18 kg or greater;
– self-propelled lawn trimmers or lawn edge trimmers;
– scissors type lawn trimmers and lawn edge trimmers;
– machines equipped with metallic cutting accessories consisting of more than one piece, e.g. pivoting chains or flail blades;
– edgers with rigid and/or metallic cutting devices.
NOTE 101 Freely pivoting non-metallic cutting elements are considered not to be rigid cutting devices.
NOTE 102 Edgers with rigid or metal cutting devices will be covered by a future part of IEC 62841-4.
NOTE 103 Annex EE provides an informative summary of characteristics for lawn trimmers, lawn edge trimmers, grass trimmers, brush cutters and brush saws.
Brush cutters and brush saws covered by this document are designed only to be operated with the machine to the right of the operator.
This clause of Part 1 is applicable, except as follows:
Addition:
This part of IEC 62841 applies to mixers. Mixers are not considered to be tools with a liquid system.
This standard does not apply to drills and impact drills, even if they can be used as a mixer.
NOTE 101 Drills and impact drills are covered by IEC 62841-2-1.
This clause of Part 1 is replaced by the following.
This part of IEC 60335 deals with the safety of electric battery chargers for household and similar use having an output not exceeding 250 V ripple-free direct current, their rated voltage being not more than 250 V.
1DV.1 DR Modification to add the following text to Clause 1 of the Part 2 after the second paragraph:
This standard covers the above-noted products that are intended to be installed or used in accordance with:
– CSA C22.1, Canadian Electrical Code (CE Code), Part I;
– NFPA 70, National Electrical Code (NEC), in the United States.
Battery chargers intended for charging batteries in a household end use application outside the scope of the IEC 60335 series of standards are within the scope of this standard.
Requirements for battery chargers for use by children at least 8 years old without supervision are given in Annex AA.
1DV.2 D2 Modification to replace the fourth paragraph of Clause 1 of the Part 2 with the following NOTE:
NOTE 101ADV Annex AA, which is a normative annex in IEC 60335-2-29, is included in this Standard as an informative annex for reference only.
Battery chargers not intended for normal household use, but which nevertheless may be a source of danger to the public, such as battery chargers intended for use in garages, shops, light industry and on farms, are within the scope of this standard.
1DV.3 D2 Modification to add the following text and NOTE 101BDV to Clause 1 of the Part 2 after the fifth paragraph:
Battery chargers intended for use in a commercial environment are within the scope of this standard.
NOTE 101BDV The following list, although not comprehensive, gives an indication of commercial environments:
– public use areas such as hotels, schools, hospitals;
– retail outlets, for example shops and supermarkets;
– business premises, for example offices and banks.
As far as is practicable, this standard deals with the common hazards presented by appliances that are encountered by all persons in and around the home. However, in general, it does not take into account
– persons (including children) whose
• physical, sensory or mental capabilities; or
• lack of experience and knowledge
prevents them from using the appliance safely without supervision or instruction;
– children playing with the appliance.
NOTE 101 Attention is drawn to the fact that
– for appliances intended to be used in vehicles or on board ships or aircraft, additional requirements may be necessary;
– in many countries additional requirements are specified by the national health authorities, the national authorities responsible for the protection of labour and similar authorities.
NOTE 102 This standard does not apply to
– built-in battery chargers, except those for installing in caravans and similar vehicles;
– battery chargers that are part of an appliance, the battery of which is not accessible to the user;
– battery chargers intended exclusively for industrial purposes;
– battery chargers intended to be used in locations where special conditions prevail, such as the presence of a corrosive or explosive atmosphere (dust, vapour or gas);
– battery chargers for emergency lighting (IEC 60598-2-22);
– supply units for electronic equipment.
1DV.4 D2 Modification to replace NOTE 102 of Clause 1 of the Part 2 with the following:
NOTE 102 This standard does not apply to
– built-in battery chargers;
– battery chargers installed on land vehicles, including caravans;
– battery chargers installed on marine craft;
– automotive battery chargers;
– battery chargers for e-mobility devices and e-bikes, provided the batteries are separately charged;
– battery chargers that are part of an appliance, the battery of which is not accessible to the user;
– battery chargers intended exclusively for industrial purposes where use by trained operators in an environment that is not accessible by the general public is relied upon as a measure of risk reduction;
– battery chargers intended to be used in locations where special conditions prevail, such as the presence of a corrosive or explosive atmosphere (dust, vapour or gas);
– battery chargers for emergency lighting;
– supply units for electronic equipment;
– battery chargers for uninterruptable power supplies;
– DC distribution boards.
1DV.5 D2 Add NOTE 103DV to Clause 1 of the Part 2:
NOTE 103DV This Part 2-29 may be employed for investigation of components and sub-assemblies for the purpose of their pre-selection for use in appliances. If the component or sub-assembly used complies with this standard, the tests for the component or sub-assembly specified in the particular appliance standard in some cases will not need to be made in the particular appliance or assembly. Additional testing on a component or subassembly might be required. For example, if a control system is associated with the particular appliance control system, additional tests could potentially be necessary on the final appliance.
This Standard describes the test procedures, test set-ups, and calculations required to determine the performance, capacities, energy consumption, and overall efficiency of compressor-cycle air-to-water heat pumps designed to be used as combination space-conditioning and potable water-heating systems “herein referred to as “combination heat pumps”.
In this Standard the performance of a combination heat pump is characterized by a set of thermal performance descriptors that provide seasonal efficiency ratings for space heating, water heating, and space cooling in a range of climates.
This Standard applies to packaged and split combination air-to-water heat pump systems and combination designs/configurations with heating capacities up to and including 19 kW (65 000 Btu/h) of total heating capacity at outdoor temperature of -8.3 °C (17 °F) and outlet water temperature of 45 °C (113 °F).
This standard applies to the following categories of combination air-to-water heat pump systems:
(a) Systems with a built-in buffer tank for heated water storage, or with a factory-supplied buffer tank that is part of the rated assembly
(b) Systems without a built-in or factory-supplied buffer tank; and
(c) Systems may be split, monobloc, or indoor-mounted single-package systems with ducted outdoor air
This standard does not apply to:
(a) solar-based or solar-assisted combination systems;
(b) systems that include a heat recovery function;
(c) consumer heat pump water heaters;
(d) pool heaters; and
(e) chillers.
In this Standard, “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the standard; “should” is used to express a recommendation or that which is advised but not required; and “may” is used to express an option or that which is permissible within the limits of the Standard.
Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material.
Notes to tables and figures are considered part of the table or figure and may be written as requirements.
Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.
The values given in SI units are the units of record for the purposes of this Standard. The values given in parentheses are for information and comparison only. All references to gallons (gal) are U.S. gallons.
1.1 General
This Standard applies to complete wind turbine electrical systems and associated electrical equipment intended for connection at not more than 46 kV and intended for use in accordance with the Canadian Electrical Code, Part I. Products covered by the scope of this Standard are subject to the requirements of CSA C22.2 No. 0.
1.2 Application
This Standard applies to wind turbines of all sizes.
1.3 Exclusions
This Standard does not apply to performance with respect to grid codes or to power performance of wind turbines.
Note: Information on test methods for power performance of wind turbines can be found in CAN/CSA C61400-12-1 and IEC 61400-12-2.
1.4 Terminology
In this Standard, “shall” is used to express a requirement, i.e. a provision that the user is obliged to satisfy in order to comply with the Standard; “should” is used to express a recommendation or that which is advised but not required; and “may” is used to express an option or that which is permissible within the limits of the Standard.
Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material.
Notes to tables and figures are considered part of the table or figure and may be written as requirements.
Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.
1.5 Units of Measurement
The values given in SI units are the units of record for the purposes of this Standard. The values given in parentheses are for information and comparison only.
1.1
This Part is intended to be read together with the Standard for Low-Voltage Fuses – Part 1: General Requirements, hereafter referred to as Part 1. The titles of the Clauses in this Part correspond to the similarly titled Clauses in Part 1. The requirements of Part 1 apply unless modified by this Part. For the Part 1 requirements, refer to the Standard for Low-Voltage Fuses – Part 1: General Requirements, NMX-J-009-248/1-ANCE / CSA C22.2 No. 248.1 / UL 248-1.
1.2
This Part applies to semiconductor fuses rated 2000 Vac or less. DC ratings are optional.
NOTE: CSA C22.1, Canadian Electrical Code, Part I, defines low voltage as any voltage exceeding 30 V but not exceeding 1000 V inclusive and high voltage as any voltage exceeding 1000 V. The National Electrical Code, NFPA 70, defines high voltage as more than 600 V, nominal.
This part of IEC 61980 addresses communication and activities of magnetic field wireless power transfer (MF-WPT) systems.
The requirements in this document are intended to be applied for MF-WPT systems according to IEC 61980-3 and ISO 19363.
The aspects covered in this document include
– operational and functional characteristics of the MF-WPT communication system and related activities, and
– operational and functional characteristics of the positioning system. The following aspects are under consideration for future documents:
– requirements for two- and three-wheel vehicles;
– requirements for MF-WPT systems supplying power to EVs in motion;
– requirements for bidirectional power transfer.
NOTE Any internal communication at supply device or EV device is not in the scope of this document
This part of IEC 61980 applies to the off-board supply equipment for wireless power transfer via magnetic field (MF-WPT) to electric road vehicles for purposes of supplying electric energy to the RESS (rechargeable energy storage system) and/or other on-board electrical systems. The MF-WPT system operates at standard supply voltage ratings per IEC 60038 up to 1 000 V AC and up to 1 500 V DC from the supply network. The power transfer takes place while the electric vehicle (EV) is stationary.
Off-board supply equipment fulfilling the requirements in this document are intended to operate with EV devices fulfilling the requirements described in ISO 19363.
The aspects covered in this document include
– the characteristics and operating conditions,
– the required level of electrical safety,
– requirements for basic communication for safety and process matters if required by a MF-WPT system,
– requirements for positioning to assure efficient and safe MF-WPT power transfer, and
– specific EMC requirements for MF-WPT systems.
The following aspects are under consideration for future documents:
– requirements for MF-WPT systems for two- and three-wheel vehicles,
– requirements for MF-WPT systems supplying power to EVs in motion,
– requirements for bidirectional power transfer,
– requirements for flush mounted primary device,
– requirements for MF-WPT systems for heavy duty vehicle, and
– requirements for MF-WPT systems with inputs greater than 11,1 kVA.
This document does not apply to
– safety aspects related to maintenance, and
– trolley buses, rail vehicles and vehicles designed primarily for use off-road.
NOTE The terms used in this document are specifically for MF-WPT.
IEC 62841-1:2014, Clause 1 is applicable, except as follows:
Addition:
This document applies to transportable single spindle vertical moulders, with a maximum tool holder diameter of 200 mm, designed to cut wood and analogue materials also covered with plastic laminate or edgings by hand-feed operation.
NOTE 101 Single spindle vertical moulders other than transportable are covered by ISO 19085-6:2024.
1.1 General
1.1.1
This Document applies to unitary air conditioners and heat pumps that are
a) factory-made;
b) air-source and air-sink;
c) single-split systems with matching assemblies or single package for use in ducted and/or non-ducted distribution systems;
d) intended for space-heating and/or air-conditioning applications in buildings;
e) electrically driven, mechanical, vapour-compression-type systems; and
f) rated below 19.0 kW (65 000 Btu/h) heating or cooling at standard rating conditions, in accordance with Clause 5.2.
1.1.2
This Document does not apply to the following:
a) water-to-air and/or water units; and
b) heat recovery.
1.2 Unitary equipment
Unitary equipment within the scope of this Document is outlined in Table 1.
1.3 Terminology
In this Document, “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with this Document; “should” is used to express a recommendation or that which is advised but not required; and “may” is used to express an option or that which is permissible within the limits of this Document.
Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material.
Notes to tables and figures are considered part of the table or figure and may be written as requirements.
Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.
1.4 Units of measurement
The values given in SI units are the units of record for the purposes of this Document. The values given in parentheses are for information and comparison only.
1.1 This Part is intended to be read together with the Standard for Low-Voltage Fuses – Part 1: General Requirements, hereafter referred to as Part 1. The titles of the Clauses in this Part correspond to the similarly titled Clauses in Part 1. The requirements of Part 1 apply unless modified by this Part. For the Part 1 requirements, refer to the Standard for Low-Voltage Fuses – Part 1: General Requirements, NMX-J-009-248/1-ANCE / CSA C22.2 No. 248.1 / UL 248-1.
1.2 This Part applies to Class J fuses rated 600 A or less and 600 V ac. DC ratings are optional.
1.1 This Part is intended to be read together with the Standard for Low-Voltage Fuses – Part 1: General Requirements, hereafter referred to as Part 1. The titles of the Clauses in this Part correspond to the similarly titled Clauses in Part 1. The requirements of Part 1 apply unless modified by this Part. For the Part 1 requirements, refer to the Standard for Low-Voltage Fuses – Part 1: General Requirements, NMX-J-009-248/1-ANCE / CSA C22.2 No. 248.1 / UL 248-1.
1.2 This Part applies to Class L fuses rated 100 – 6000 A and 600 V ac. DC ratings are optional.
1.1 General
This Standard specifies the requirements for zinc coating (galvanizing) both by the hot-dipping process and thermal diffusion on iron and steel products intended or primarily for use in electrical and communication systems, made from rolled, pressed, cast iron, or forged shapes such as structural sections, plates, bars, pipes, or sheets 1 mm thick and thicker. Which specific galvanizing process is to be used shall be agreed upon by the buyer and galvanizer at the time of order.
1.2 Inclusions
This Standard applies to;
a) both unfabricated and fabricated products such as assembled steel products, structural steel fabrications, large hollow sections bent or welded before galvanizing, and wire work fabricated from uncoated steel wire; and
b) steel forgings and iron castings that are to be galvanized separately or in batches.
1.3 Exclusions
This Standard does not apply to;
a) the continuous galvanizing of chain link fence fabric, wire, sheet, and strip; and
b) pipe and conduit that are normally hot dip galvanized by a continuous or semicontinuous automatic process.
1.4 Terminology
In this Standard, “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the standard; “should” is used to express a recommendation or that which is advised but not required; and “may” is used to express an option or that which is permissible within the limits of the Standard.
Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material.
Notes to tables and figures are considered part of the table or figure and may be written as requirements.
Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.