- Emergency lighting equipment (New Edition) ...
- DRAFT STANDARD
- Legal Notice for Draft Standards
- Preface
- + 1 Scope
- 1.1 Classification
- 1.2 Application
- 1.3 Terminology
- 1.4 Dual measurements
- 2 Reference publications
- 3 Definitions
- + 4 General requirements
- 4.1 General
- + 4.2 Components
- 4.2.1 General
- 4.2.2 Flammability ratings
- + 4.3 Output rating
- 4.3.1 Unit equipment and emergency luminaires w...
- 4.3.2 Central power systems
- 4.3.3 Rated discharged time
- + 4.4 Equipment performance
- 4.4.1 Criteria — Unit equipment
- 4.4.2 Criteria — Emergency luminaires
- 4.4.3 Criteria — Central power systems
- + 4.4.4 Operating conditions
- 4.4.4.1
- 4.4.4.2
- 4.4.4.3
- 4.4.5 Operation at extreme temperatures
- 4.4.6 Compliance
- + 4.5 Indication of operating condition
- + 4.5.1 Signal devices
- 4.5.1.1
- 4.5.1.2
- 4.5.1.3
- 4.5.1.4
- 4.5.1.5
- 4.5.2 Phase failure
- 4.5.3 Equipment with auto-testing/auto-diagnost...
- 4.6 Testing of operation of equipment with batt...
- + 5 Construction
- + 5.1 General
- 5.1.1 Central power systems
- 5.1.2 Electrical components
- 5.1.3 Equipment securement
- 5.1.4 Inspection access
- 5.1.5 Vented-type storage battery inspection
- 5.1.6 Equipment battery lifting requirements
- 5.1.7 Equipment supporting additional mass
- 5.1.8 Swivel joint rotation limitation
- 5.1.9 Remote luminaires
- 5.1.10 Conductively coupled circuits
- 5.1.11 Thermal protection
- + 5.2 Enclosures
- + 5.2.1 General
- 5.2.1.1
- 5.2.1.2
- 5.2.1.3
- 5.2.1.4
- 5.2.1.5
- 5.2.1.6
- 5.2.2 Non-metallic materials
- 5.2.3 Thickness of sheet metal enclosures for l...
- 5.2.4 Thickness of cast enclosures for live par...
- Table 1
- Table 2
- + 5.2.5 Openings in enclosures
- 5.2.5.1
- 5.2.5.2
- 5.2.5.3
- 5.2.5.4
- 5.2.6 Doors and covers of enclosures
- + 5.3 Mechanical assembly
- 5.3.1 Fastening of electrical components
- 5.3.2 Equipment protection against corrosive li...
- 5.3.3 Enclosure of switch and relay contacts
- + 5.4 Supply connections
- + 5.4.1 General
- 5.4.1.1
- 5.4.1.2
- + 5.4.2 Cord-connected equipment
- 5.4.2.1
- 5.4.2.2
- 5.4.2.3
- 5.4.2.4
- 5.4.2.5
- 5.4.2.6
- + 5.4.3 Equipment for permanent connection
- 5.4.3.1
- 5.4.3.2
- 5.4.3.3
- 5.4.3.4
- 5.4.3.5
- 5.4.3.6
- + 5.4.4 Strain relief
- 5.4.4.1
- 5.4.4.2
- 5.4.4.3
- 5.4.4.4
- 5.5 Bushings
- + 5.6 Current-carrying parts
- 5.6.1 Material suitability
- 5.6.2 Securing bare live parts
- + 5.7 Wiring
- + 5.7.1 General
- 5.7.1.1
- 5.7.1.2
- 5.7.1.3
- 5.7.1.4
- 5.7.1.5
- 5.7.1.6
- + 5.7.2 Wiring materials
- 5.7.2.1
- 5.7.2.2
- + 5.7.3 Minimum conductor size
- 5.7.3.1
- 5.7.3.2
- 5.7.3.3
- + 5.8 Electrical insulation
- 5.8.1 Support of bare live parts
- 5.8.2 Insulating material suitability
- 5.8.3 Insulation restrictions
- 5.8.4 Insulation requirements
- + 5.9 Storage batteries
- 5.9.1 Requirements for replacement storage batt...
- 5.9.2 Visual indication of electrolyte level fo...
- 5.9.3 Battery certification requirements
- + 5.10 Charging means
- 5.10.1 Charging means maintenance
- 5.10.2 Electrical isolation of input and output...
- + 5.11 Output connections
- + 5.11.1 General
- 5.11.1.1
- 5.11.1.2
- 5.11.1.3
- 5.11.1.4
- 5.11.2 Overcurrent protection
- 5.11.3 Disconnecting means
- + 5.12 Fuses
- 5.12.1 Use of plug fuses
- 5.12.2 Connection of fuseholders
- 5.12.3 Location of fuses
- 5.13 Transformers
- + 5.14 Switches and controls
- 5.14.1 Switches and controls compliance
- 5.14.2 Switch and control device suitability
- + 5.15 Signal lights
- 5.15.1 Lampholder screwshell terminal connectio...
- 5.15.2 Lampholders having paper liners
- 5.15.3 Protection of signal lights
- + 5.16 Spacings
- 5.16.1 Minimum spacing requirements
- 5.16.2 Spacing of bare live parts
- 5.16.3 Spacing requirements when using barriers...
- + 5.17 Separation of circuits
- 5.17.1 Separation of internal conductors
- 5.17.2 Separation by use of barriers
- 5.17.3 Separation of field wiring connections f...
- + 5.18 Bonding
- 5.18.1 Bonding for emergency luminaires, exit s...
- 5.18.2 Bonding for remote extra-low-voltage lum...
- 5.19 Lamps
- + 5.20 Swivels
- 5.20.1 Swivel joints of luminaires test require...
- 5.20.2 Swivel joint material requirements
- 5.21 Visibility requirements
- + 5.22 Equipment operating as emergency lighting ...
- 5.22.1
- 5.22.2
- + 6 Marking
- 6.1 General
- + 6.2 Identification and ratings
- 6.2.1 Identification markings
- 6.2.2 Input ratings
- 6.2.3 Output ratings
- 6.2.4 Class 2 output circuits
- + 6.3 Installation and maintenance
- 6.3.1 Fuse identification
- 6.3.2 Equipment supporting additional mass
- 6.3.3 Emergency equipment having two power sour...
- 6.3.4 Legend for visual diagnostic status
- 6.3.5 Lamp replacement identification
- 6.3.6 High-frequency inverters
- 6.3.7 Battery identification
- + 6.4 Exit signs
- 6.4.1 General
- 6.4.2 Enhanced visibility exit signs
- 6.4.3 Flashing exit signs
- 6.5 Central power systems
- + 6.6 Directly-controlled emergency luminaires
- Table 8
- Table 9
- Table 10
- + 7 Tests
- + 7.1 General
- 7.1.1 Central power systems compliance
- 7.1.2 Equipment without batteries
- 7.1.3 Test order
- 7.1.4 Minimum end-of-discharge voltage
- + 7.2 Conditions for test
- 7.2.1 Test voltage
- 7.2.2 Test frequency
- 7.2.3 Equipment mounting
- + 7.2.4 Test ambient temperature
- 7.2.4.1 General
- 7.2.4.2 Equipment operating at extreme ambient ...
- 7.2.5 Battery load during discharge tests
- 7.2.6 Battery discharge limiting devices
- 7.2.7 Additional test materials
- + 7.3 Preparation of equipment with batteries
- 7.3.1 Preparation for testing
- 7.3.2 Initial battery charging
- + 7.4 Rating (input)
- 7.4.1 Maximum input current and power measureme...
- 7.4.2 Equipment with batteries
- 7.4.3 Equipment without batteries
- 7.4.4 Maximum input tolerance
- + 7.5 Charging means
- 7.5.1 Concurrent testing
- 7.5.2 Charging means measurement for other than...
- 7.5.3 Charging means measurement for lithium ba...
- 7.5.4 Suitability of charging means
- + 7.6 Temperatures
- 7.6.1 Concurrent testing
- 7.6.2 Test ambient conditions
- 7.6.3 Maximum temperatures for equipment with b...
- 7.6.4 Temperature test thermal limits
- 7.6.5 Equivalent temperature evaluation
- 7.6.6 Testing of remote luminaires
- 7.6.7 Equipment with an automatic control relay...
- Table 4
- Figure 1
- 7.7 Over-voltage test — Extreme input voltage
- + 7.8 Leakage current
- 7.8.1 General
- 7.8.2 Measurement equipment
- 7.8.3 Test procedure
- Figure 2
- Figure 3
- + 7.9 Dielectric strength
- 7.9.1 All equipment
- 7.9.2 Equipment with extra-low voltage input
- 7.9.3 Electrical isolation of input and output ...
- 7.9.4 Voltage-limiting clamping devices and lin...
- 7.9.5 Use of a dc potential
- + 7.10 Battery discharge test
- 7.10.1 General
- 7.10.2 Charging time
- 7.10.3 Test procedure
- 7.10.4 Battery capacity
- 7.11 Minimum ambient temperature
- + 7.12 Minimum extreme voltage
- 7.12.1 Minimum voltage cycle
- 7.12.2 Minimum voltage compliance
- + 7.13 Electrolyte loss
- 7.13.1 Batteries with free electrolyte
- 7.13.2 Battery electrolyte loss measurement
- 7.13.3 Electrolyte loss limit for batteries wit...
- + 7.14 Light output
- 7.14.1 Interior ambient light level
- 7.14.2 Test for suitable lamps
- 7.14.3 Test equipment requirements
- 7.14.4 Basic measuring procedure for battery-op...
- 7.14.5 Basic measuring procedure for inverter-o...
- 7.14.6 Light output factors
- + 7.15 Lamp life
- 7.15.1 Testing of lamps
- 7.15.2 Lamp cycling
- 7.15.3 Lamp burnout
- 7.16 Swivel test
- + 7.17 Lifting harnesses
- 7.17.1 Lifting harness requirements for batteri...
- 7.17.2 Electrolyte immersion test
- 7.18 Minimum light output for emergency lightin...
- 7.19 Energy performance and relevant markings f...
- + 7.20 Component breakdown
- 7.20.1 General
- 7.20.2 Component testing
- 7.20.3 Test procedure
- 7.20.4 Component testing compliance
- + 7.21 Abnormal test for equipment containing lit...
- 7.21.1 Initial battery conditions
- 7.21.2 Equipment conditions
- 7.21.3 Operation under simulated fault conditio...
- 7.21.4 Battery temperature and voltage measurem...
- 7.21.5 Battery performance conditions
- 7.22 Operation of equipment with auto-testing/a...
- + 7.23 Central power system testing
- 7.23.1 Output voltage and frequency test
- 7.23.2 Output load and power factor test
- 7.23.3 Battery discharge test
- 7.23.4 Overload testing
- 7.23.5 Phase failure
- 7.23.6 Central system indicator
- + 7.24 Operation of equipment with emergency ligh...
- 7.24.1
- 7.24.2
- 7.24.3
- 7.24.4
- + 8 Impedance networks
- + 8.1 Application
- 8.1.1 Supplementary requirements
- 8.1.2 Unit equipment with non-isolating charger...
- 8.1.3 Central station battery systems and unit ...
- + 8.2 General requirements
- 8.2.1 General
- 8.2.2 Low-voltage power-limited circuits
- + 8.3 Construction
- 8.3.1 Coupling capacitors
- 8.3.2 Electronic circuits
- + 8.3.3 High-frequency inverters
- 8.3.3.1
- 8.3.3.2
- 8.3.3.3
- + 8.4 Tests
- + 8.4.1 General
- 8.4.1.1
- 8.4.1.2
- + 8.4.2 Output voltage and current test
- 8.4.2.1
- 8.4.2.2
- 8.4.2.3
- 8.4.2.4
- 8.4.2.5
- 8.4.2.6
- + Table 5
- Table 6
- + 8.4.3 Abnormal test
- 8.4.3.1
- 8.4.3.2
- 8.4.3.3
- 8.4.3.4
- 8.4.3.5
- 8.4.3.6
- + Annex A (normative)
- + A.1 General
- A.1.1
- A.1.2
- + A.2 General requirements
- A.2.1 General
- A.2.2 Illumination
- A.2.3 Diffuser flammability
- + A.3 Sign construction
- + A.3.1 Legends
- A.3.1.1 General
- A.3.1.2 Stroke width
- A.3.1.3 Aspect ratio of characters
- A.3.1.4 Bilingual legends
- A.3.1.5 Edge-lit signs
- + A.3.2 Directional indicators
- A.3.2.1 Size and shape
- A.3.2.2 Location
- A.3.2.3 Permanence
- A.3.3 Background
- + A.4 General test requirements
- A.4.1 Ambient conditions
- + A.4.2 Preparation for testing
- A.4.2.1 Lamp seasoning
- A.4.2.2 Lamp warm-up
- + A.4.3 Electrical supply characteristics
- A.4.3.1 AC power supply
- A.4.3.2 DC power supply
- + A.4.4 Instrumentation
- A.4.4.1 General
- A.4.4.2 Photometers
- A.4.4.2.1
- A.4.4.2.2
- A.4.4.2.3
- A.4.4.3 Electrical instruments
- + A.5 Luminance requirements
- + A.5.1 Exit signs in the non-energized state
- A.5.1.1 Test conditions
- A.5.1.2 Luminance uniformity within the legend
- A.5.1.3 Luminance uniformity across the backgro...
- A.5.1.4 Luminance contrast
- A.5.1.5 Luminance contrast of concealing mechan...
- + A.5.2 Exit signs using normal ac power
- A.5.2.1 Test conditions
- + A.5.2.2 Luminance uniformity within legends and...
- A.5.2.2.1 Luminous legends and directional indi...
- A.5.2.2.2 Non-luminous legends and directional ...
- + A.5.2.3 Luminance uniformity across the backgro...
- A.5.2.3.1 Luminous backgrounds
- A.5.2.3.2 Non-luminous backgrounds
- A.5.2.4 Luminance contrast
- A.5.2.5 Luminance contrast of concealing mechan...
- A.5.2.6 Minimum luminance of a luminous element...
- A.5.2.6.1
- A.5.2.6.2
- A.5.2.6.3
- + A.5.3 Exit signs using emergency dc power
- A.5.3.1 Test conditions
- A.5.3.2 Luminance uniformity within legends and...
- A.5.3.2.1 Luminous legends and directional indi...
- A.5.3.2.2 Non-luminous legends and directional ...
- A.5.3.3 Luminance uniformity across the backgro...
- A.5.3.3.1 Luminous backgrounds
- A.5.3.3.2 Non-luminous backgrounds
- A.5.3.4 Luminance contrast
- A.5.3.5 Luminance contrast of concealing mechan...
- A.5.3.6 Minimum luminance of a luminous element...
- A.5.3.6.1
- A.5.3.6.2
- A.5.3.6.3
- + A.6 Luminance measurements
- A.6.1 General
- + A.6.2 Illuminance apparatus
- A.6.2.1
- A.6.2.2
- + A.6.3 Luminous legend and directional indicator...
- A.6.3.1
- A.6.3.2
- A.6.3.3
- A.6.3.4
- + A.6.4 Background
- A.6.4.1
- A.6.4.2
- A.6.4.3
- A.6.4.4
- + A.7 Luminance calculations
- A.7.1 Contrast formula
- A.7.2 Mean luminance of the legend
- A.7.3 Mean luminance of the background
- Table A.1
- Table A.2
- Table A.3
- Figure A.1
- Figure A.2
- Figure A.3
- Figure A.5
- Figure A.6
- Figure A.7
- Figure A.8
- Figure A.9
- Figure A.10
- + Annex B (normative)
- B.1 General
- + B.2 General requirements
- B.2.1 General
- B.2.2 Illumination
- + B.2.3 Requirements for translucent pictogram le...
- B.2.3.1 Flammability requirements
- B.2.3.2 Mechanical rigidity
- + B.3 Sign construction
- B.3.1 General
- B.3.2 Legends
- B.3.3 Directional indicator
- B.3.4 Pictogram sign with additional elements
- + B.3.5 Colourimetric and photometric properties ...
- B.3.5.1 Conditions
- B.3.5.2 Colour requirements
- B.3.6 Permanence
- B.3.7 Enhanced visibility signs
- B.3.8 Flashing signs
- + B.4 General test requirements
- B.4.1 Test temperature conditions
- + B.4.2 Preparation for testing
- B.4.2.1 Lamp seasoning
- B.4.2.2 Lamp warm-up
- + B.4.3 Electrical supply characteristics
- B.4.3.1 AC power supply
- B.4.3.2 DC power supply
- + B.4.4 Instrumentation
- B.4.4.1 General
- B.4.4.2 Photometers
- B.4.4.2.1
- B.4.4.2.2
- B.4.4.2.3
- B.4.4.3 Electrical instruments
- + B.5 Luminance requirements
- + B.5.1 Exit signs using normal ac power
- B.5.1.1 Test conditions
- B.5.1.2 Luminance levels and uniformity within ...
- B.5.1.2.1
- B.5.1.2.2
- B.5.1.3 Luminance uniformity within white colou...
- B.5.1.4 Luminance contrast ratio between white ...
- B.5.1.5 Flashing rate
- B.5.1.6 Flashing duty cycle
- + B.5.2 Exit signs using emergency dc power
- B.5.2.1 Test conditions
- B.5.2.2 Luminance
- B.5.2.3 Luminance level for enhanced visibility...
- B.5.2.4 Luminance for exit signs in flashing mo...
- + B.6 Measurement methodology
- B.6.1 General
- + B.6.2 Safety green colour and contrast white co...
- B.6.2.1
- B.6.2.2
- B.6.2.3
- B.6.2.4
- B.6.3 Flashing rate, light pulse duration, and ...
- Table B.1
- Table B.2
- Table B.3
- Figure B.1
- Figure B.2
- Figure B.3
- Figure B.4
- Figure B.5
- Figure B.6
- Figure B.7
- + Annex C (normative)
- C.1 General
- + C.2 Performance
- C.2.1
- C.2.2
- C.2.3
- C.2.4
- C.2.5
- C.2.6
- C.2.7
- C.2.8
- + C.3 Marking
- C.3.1
- C.3.2
- C.3.3
- + Annex D (normative)
- + D.1 Diffuser — Flammability requirements
- D.1.1 General
- D.1.2 Diffuser material used for more than one ...
- D.1.3 Diffuser material enclosing live parts
- D.1.4 Diffuser material requiring an additional...
- + D.2 Exit signs with limited risk of fire and el...
- D.2.1 Exit signs using a limited power source
- D.2.2 Exit signs supplied by other power source...
- + D.3 Thermal conditioning test
- D.3.1
- D.3.2
- D.3.3
- + Annex E (normative)
- E.1 General
- E.2 Mounting and installation
- E.3 Tests
- + E.4 Marking and instructions
- E.4.1 General requirements
- + E.4.2 Markings
- E.4.2.1 General
- E.4.2.2 Installation
- E.4.2.3 Extreme ambient temperature use
- E.4.2.4 Emergency battery packs using lamps
- E.4.2.5 Drilling or punched openings
- + E.4.3 Instructions
- E.4.3.1 General
- E.4.3.2 Making or altering openings in an enclo...
- E.4.3.3 Installation within an enclosure
- E.4.3.4 Derangement signals
- E.4.3.5 Replacement lamps
- Annex F (informative)
1.1 Classification
This Standard applies to exit signs, unit equipment which may contain an inverter, emergency luminaires, and central power systems intended for connection to circuits with nominal voltages of 600 V and less, and providing illumination in the event of a failure of the normal power supply for non-hazardous locations in accordance with the Canadian Electrical Code, Part I.
1.2 Application
This Standard includes requirements for the construction of emergency lighting equipment to preclude fire and electric shock hazards, and to ensure the equipment has the minimum capability for performing its intended function.
1.3 Terminology
In this Standard, “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the Standard; “should” is used to express a recommendation or that which is advised but not required; and “may” is used to express an option or that which is permissible within the limits of the Standard.
Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material.
Notes to tables and figures are considered part of the table or figure and may be written as requirements.
Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.
1.4 Dual measurements
The values given in SI units are the units of record for the purposes of this Standard. The values given in parentheses are for information and comparison only.
You may comment on any section of this document by clicking the “Submit Comment” link at the bottom of the relevant section.