Draft Details
- Portable and stationary electric signs and dis...
- DRAFT STANDARD
- Legal Notice for Draft Standards
- Preface
- 0 Introduction
- + 1 Scope
- 1.1
- 1.2
- 1.3
- 1.4
- 1.5
- 1.6
- 1.7
- 2 References
- 3 Definitions
- + 4 General
- 4.1 General requirements
- 4.2 Sign construction
- 4.3 Components
- + 5 Mechanical construction
- + 5.1 General
- 5.1.1 Signs with PV modules and batteries
- 5.1.2 Hinged parts
- 5.1.3 Sharp edges
- + 5.2 Sign body
- 5.2.1 General
- 5.2.2 Materials
- + 5.2.3 Openings in a sign body
- 5.2.3.1 General
- 5.2.3.2 Ventilating openings
- + 5.2.3.3 Drain holes
- 5.2.3.3.1 General
- 5.2.3.3.2 Drain hole exception
- + 5.2.4 Channel letters
- 5.2.4.1 General
- 5.2.4.2 Channel letters used as an enclosure
- + 5.2.5 Sign face
- 5.2.5.1 General
- 5.2.5.2 Rigid material
- 5.2.5.3 Flexible materials
- + 5.2.6 Recessed signs
- 5.2.6.1 General
- 5.2.6.2 Materials
- + 5.2.6.3 Openings in a recessed sign body
- 5.2.6.3.1 General
- 5.2.6.3.2 Mounting holes
- 5.2.6.3.3 Recessed sign body serving as an enc...
- 5.2.6.3.4 Open holes in Type Non-IC signs
- 5.2.6.3.5 Open holes in Type IC signs
- 5.2.6.3.6 Other holes sizes in a recessed sign...
- + 5.3 Enclosures
- 5.3.1 General
- 5.3.2 Metal enclosures
- Table 5.3.1
- Table 5.3.2
- Table 5.3.3
- Table 5.3.4
- + 5.3.3 Polymeric enclosure materials
- 5.3.3.1 General
- 5.3.3.2 Polymeric enclosure materials for chann...
- + 5.3.4 Glass enclosures
- 5.3.4.1 General
- 5.3.4.2 Glass thickness and exposed area
- 5.3.4.3 Glass securement
- + 5.3.5 Openings in enclosures
- 5.3.5.1 General
- 5.3.5.2 Ventilating openings in an enclosure
- 5.3.5.3 Drain holes in an enclosure
- 5.3.6 Conduit knockouts and twist-outs
- 5.3.7 Baffles
- + 5.3.8 Recessed junction boxes
- 5.3.8.1 General
- 5.3.8.2 Materials
- 5.4 Corrosion protection
- + 5.5 Barriers and insulating materials
- + 5.5.1 Accessibility barriers
- 5.5.1.1 General
- 5.5.1.2 Materials
- 5.5.1.3 Polymeric materials
- 5.5.1.4 Tests for accessibility barriers
- 5.5.2 Insulating barriers
- 5.5.3 Insulating materials
- 5.5.4 Barrier securement
- + 5.6 Raceways
- 5.6.1 General
- 5.6.2 Raceway tubing
- 5.7 Conductor protection
- + 5.8 Mechanical joints and fastenings
- 5.8.1 General
- 5.8.2 Spacing of fastenings
- 5.8.3 Screws
- 5.8.4 Adhesives
- + 5.9 Means of mounting and support
- 5.9.1 Supporting frames
- + 5.9.2 Stationary signs
- 5.9.1.1 Permanently installed
- 5.9.1.2 Free-standing
- + 5.9.3 Canopy signs
- + 5.9.3.1 Support by an outlet box
- 5.9.3.1.1 General
- 5.9.3.1.2 Mounting straps, plates, and crossba...
- 5.9.3.1.3 Inspection after installation
- 5.9.3.1.4 Access openings
- 5.9.3.2 Support independent of an outlet box
- 5.9.3.3 Pendant mounting
- 5.9.3.4 Provided with a hanging means
- 5.9.4 Recessed signs
- 5.9.5 Trailer-mounted signs
- 5.9.6 Portable signs
- 5.9.7 Use of polymeric materials for mounting
- + 5.10 Strain relief
- 5.10.1 General
- 5.10.2 Strain relief for a power supply cord
- 5.10.3 Strain relief for field wiring
- + 5.11 Poles
- 5.11.1 General
- 5.11.2 Materials
- 5.11.3 Splice compartment
- 5.11.4 Additional requirements
- + 5.12 Sectional signs
- 5.12.1 General
- 5.12.2 Sectional sign bodies
- 5.12.3 Mounting and support
- + 5.13 Digital display signs
- 5.13.1 General
- 5.13.2 Sectional digital display signs
- 5.13.3 Tests
- + 5.14 Controllers, dimmers, and flashers
- 5.14.1 General
- 5.14.2 Component equipment
- 5.14.3 Field-installed equipment
- 5.14.4 Portable equipment
- 5.14.5 Tests
- + 5.15 Clocks and clock mechanisms
- 5.15.1 General
- 5.15.2 Mounting
- 5.15.3 Moving parts
- + 5.16 High-voltage luminous-discharge-tube signs...
- 5.16.1 General
- 5.16.2 High-voltage luminous-discharge-tube con...
- 5.16.3 High-voltage luminous-discharge-tube sig...
- + 6 Electrical construction
- + 6.1 Supply connections
- 6.1.1 General
- 6.1.2 Field-wiring terminals
- 6.1.3 Field-wiring leads
- + 6.1.4 Stationary signs
- 6.1.4.1 General
- 6.1.4.2 Cord-connected
- + 6.1.5 Portable signs
- 6.1.5.1 General
- 6.1.5.2 Indoor portable signs
- 6.1.5.3 Outdoor portable signs
- + 6.1.6 Sectional signs
- 6.1.6.1 General
- 6.1.6.2 Splice enclosures
- 6.1.7 Supply connections for Class 2, SELV, or ...
- + 6.2 Wiring
- 6.2.1 General
- 6.2.2 Equipment wire
- 6.2.3 Security and protection of wiring
- + 6.2.4 Splices and connections
- 6.2.4.1 Splices
- 6.2.4.2 Wire connectors
- 6.2.5 Class 2, SELV, or LPS wiring
- + 6.2.6 High voltage wiring
- 6.2.6.1 General
- 6.2.6.2 Supports for high-voltage wiring
- 6.2.6.3 Spacings for high-voltage wiring
- 6.2.6.4 High-voltage wiring interconnections
- 6.3 Identification and polarity
- + 6.4 Bonding and grounding
- 6.4.1 General
- 6.4.2 Parts not required to be bonded to ground...
- 6.4.3 Stationary signs
- 6.4.4 Portable signs
- 6.4.5 Canopy signs
- + 6.4.6 Sign components
- 6.4.6.1 General
- + 6.4.6.2 Terminals
- 6.4.6.2.1 General
- 6.4.6.2.2 Pressure wire terminals
- 6.4.6.2.3 Wire-binding screws or studs
- Figure 6.4.6.1
- Table 6.4.6.2
- 6.4.6.3 Leads
- 6.4.6.4 Cord-connected
- 6.5 Separation of circuits
- + 6.6 Spacings
- 6.6.1 Electrical spacings
- Table 6.6.1
- Table 6.6.2
- Table 6.6.3
- Table 6.6.4
- + 6.6.2 Component spacing
- 6.6.2.1 General
- 6.6.2.2 Power unit spacing
- 6.6.2.3 Combustible materials
- 6.6.2.4 Internal wiring
- 6.6.2.5 Thermal spacings
- + 6.7 Accessibility of live parts and moving part...
- 6.7.1 General
- 6.7.2 Accessibility of uninsulated live parts
- 6.7.3 Accessibility of insulated live parts
- + 6.7.4 Accessibility of live parts for high-volt...
- 6.7.4.1 Uninsulated live parts
- 6.7.4.2 Insulated live parts
- 6.7.4.3 Accessibility barriers
- 6.7.4.4 Transformers and power supplies
- 6.7.4.5 Neon tubing electrodes
- 6.7.4.6 Tamper-resistant neon tubing electrode ...
- + 6.8 Disconnecting means
- 6.8.1 Integral to a sign
- 6.8.2 Remote disconnecting means
- 6.9 Printed wiring boards
- + 6.10 Lampholders and lamps
- + 6.10.1 Lampholders
- 6.10.1.1 General
- 6.10.1.2 Fluorescent lampholders
- 6.10.1.3 Lampholders for HID lamps
- 6.10.1.4 Lampholders for high-voltage luminous-...
- 6.10.1.5 Mounting
- + 6.10.2 Lamps
- 6.10.2.1 Incandescent
- 6.10.2.2 Self-ballasted lamps
- 6.10.2.3 HID lamps
- 6.10.3 Lamp containment barriers
- + 6.11 Ballasts, transformers, and power supplies...
- 6.11.1 General
- 6.11.2 Usage and support
- 6.11.3 For fluorescent and HID lamps
- 6.11.4 For high-voltage luminous-discharge-tube...
- + 6.11.5 For LED light sources
- 6.11.5.1 General
- 6.11.5.2 Transformers
- 6.11.5.3 Power units
- 6.11.6 For digital display signs
- 6.12 LED arrays or modules
- + 6.13 LED or LCD displays
- 6.13.1 General
- 6.13.2 Class 2, SELV, or LPS displays
- 6.13.3 Non-Class 2, SELV, or LPS displays
- 6.13.4 Interconnection of LED or LCD displays
- 6.13.5 Tests
- + 6.14 Protective devices
- 6.14.1 Thermal protective devices
- 6.14.2 Over-current protective devices
- 6.14.3 Fuses
- + 6.14.4 Switches
- 6.14.4.1 General
- 6.14.4.2 Other than single-pole type
- 6.14.4.3 Single-pole types
- + 6.15 Gaskets and bushings
- 6.15.1 General
- 6.15.2 Material requirements
- 6.15.3 Securement means
- 6.15.4 Securement by adhesive
- 6.16 Receptacles
- 6.17 Fans
- + 7 Marking and instructions
- 7.1 General
- 7.2 Permanent markings
- + 7.3 All signs
- 7.3.1 General
- 7.3.2 Fuse markings
- 7.3.3 Receptacles
- 7.3.4 Hinged parts
- 7.3.5 Replacement lamps
- 7.3.6 Environmental suitability
- + 7.3.7 Installation instructions
- 7.3.7.1 General
- 7.3.7.2 Multi-housing signs
- 7.3.7.3 Class 2 input
- 7.3.7.4 Flexible sign faces
- 7.3.7.5 Installation instructions linked with a...
- 7.4 Stationary signs
- 7.5 Recessed signs
- 7.6 Portable signs
- 7.7 Trailer mounted signs
- + 7.8 Sectional signs
- 7.8.1 General
- 7.8.2 Environmental suitability of each section...
- 7.8.3 Installation instructions
- 7.9 Outline lighting
- 7.10 High-voltage luminous-discharge-tube signs...
- + 7.11 Controllers, dimmers, and flashers
- 7.11.1 Markings
- 7.11.2 Installation instructions
- Table 7.1
- Table 7.2
- Table 7.3
- + 8 Tests
- + 8.1 General
- 8.1.1 Cheesecloth
- 8.1.2 Thermocouples for temperature measurement...
- 8.1.3 Coil and winding temperature measurements...
- 8.2 Maximum input current
- + 8.3 Temperature
- 8.3.1 Lamps and light sources
- 8.3.2 Ambient conditions and measurement
- 8.3.3 Mounting or support
- 8.3.4 Temperature measurements
- + 8.4 Abnormal conditions
- 8.4.1 Abnormal operation
- 8.4.2 Abnormal temperature conditions
- 8.4.3 Component failure
- 8.4.4 Test conditions
- 8.4.5 Test duration and failure criteria
- + 8.5 Dielectric voltage withstand test
- 8.5.1 Test apparatus
- 8.5.2 Signs and components
- 8.5.3 Accessibility barriers
- + 8.6 Leakage current test
- 8.6.1 General
- 8.6.2 Test equipment
- 8.6.3 Leakage current measurement
- Figure 8.6.1
- Figure 8.6.2
- + 8.7 Bonding circuit impedance
- 8.7.1 Resistance measurement
- 8.7.2 Impedance measurement
- 8.8 Exclusion of water test
- 8.9 Rain test
- Table 8.9.1
- Figure 8.9.1
- Figure 8.9.2
- + 8.10 Strain relief
- 8.10.1 Strain relief for flexible cords
- 8.10.2 Strain relief for conductors
- 8.11 Flaming oil
- + 8.12 Strength and rigidity tests
- 8.12.1 Barrier strength
- 8.12.2 Junction box rigidity
- 8.13 Flexible sign face material test
- + 8.14 Impact test
- 8.14.1 Ball impact
- Figure 8.14.1
- Figure 8.14.2
- 8.14.2 Drop impact
- + 8.15 Glass impact tests
- 8.15.1 Glass fragmentation test
- 8.15.2 Glass impact test
- 8.16 Loading test
- 8.17 Stability test
- + 8.18 Gasket tests
- 8.18.1 Gasket assembly accelerated aging
- + 8.18.2 Gasket accelerated aging
- 8.18.2.1 Method A
- 8.18.2.2 Method B
- 8.18.3 Gasket adhesion
- + 8.19 Adhesive tests
- 8.19.1 General
- 8.19.2 Baseline test
- 8.19.3 Temperature test
- 8.19.4 Humidity test
- 8.19.5 Cold test
- 8.19.6 Thermal cycling test
- + 8.20 Lamp containment barrier tests
- 8.20.1 Lamp containment barrier thermal shock
- 8.20.2 Lamp containment barrier melt through
- 8.21 Mold stress
- 8.23 Conduit knockout and twistout
- + 8.24 Screw torque tests
- 8.24.1 Self threading screw torque
- 8.24.2 Ground-screw assembly strength
- 8.25 UV resistance test
- 8.26 Overload test
- 8.27 Endurance test
- 8.28 Stamped ink markings test
- 8.29 Hinged parts test
- + Annex A (normative)
- A.1 Scope
- A.2 Definitions
- + A.3 Construction
- A.3.1 General
- + A.3.2 Materials
- A.3.2.1 General
- A.3.2.2 Glass
- + A.4 Components for use only in an end product
- + A.4.1 Electrode receptacles
- A.4.1.1 General
- + A.4.1.2 Construction
- A.4.1.2.1 General
- A.4.1.2.2 Insulating material
- A.4.1.2.2 Supply connection
- A.4.1.2.3 Drain holes
- A.4.1.2.4 Spring contacts
- A.4.1.3 Tests
- + A.4.2 Feed type lampholders (over 1000V)
- A.4.2.1 General
- + A.4.2.2 Construction
- A.4.2.2.1 General
- A.4.2.2.2 Insulating material
- A.4.2.2.3 Damp locations
- A.4.2.2.4 Wet locations
- A.4.2.3 Tests
- + A.4.3 Interconnecting lampholders (over 1000V) ...
- A.4.3.1 General
- + A.4.3.2 Construction
- A.4.3.2.1 General
- A.4.3.2.2 Insulating material
- A.4.3.2.3 Damp locations
- A.4.3.2.4 Wet locations
- + A.4.3.3 Tests
- A.4.3.3.1 General
- A.4.3.3.2 Polymeric materials
- + A.4.4 Electrode receptacle enclosures
- A.4.4.1 General
- A.4.4.2 Construction
- + A.4.4.3 Tests
- A.4.4.3.1 General
- A.4.4.3.2 Dry locations only
- A.4.4.3.3 Damp locations
- + A.4.5 Polymeric neon electrode enclosures
- A.4.5.1 General
- A.4.5.2 Construction
- + A.4.5.3 Tests
- A.4.5.3.1 General
- A.4.5.3.2 Dry locations
- A.4.5.3.3 Damp locations
- A.4.5.3.4 Wet locations
- A.4.5.3.5 Dielectric tests
- A.4.5.3.6 Additional tests
- + A.4.6 GTO cable splice enclosures
- A.4.6.1 General
- A.4.6.2 Construction
- + A.4.6.3 Tests
- A.4.6.3.1 General
- A.4.6.3.2 Dry locations only
- A.4.6.3.3 Damp locations
- A.4.6.3.4 Wet locations
- + A.4.7 Electrode receptacle insulator
- A.4.7.1 General
- A.4.7.2 Construction
- A.4.7.3 Tests
- + A.4.8 GTO cable sleeves
- A.4.8.1 Construction
- + A.4.8.2 Tests
- A.4.8.2.1 General
- A.4.8.2.2 Dry locations
- A.4.8.2.3 Damp locations
- A.4.8.2.4 Wet locations
- A.4.8.2.5 Dielectric tests
- + A.5 Components for field installation
- + A.5.1 Neon transformer enclosures
- A.5.1.1 Construction
- A.5.1.2 Tests
- + A.5.2 Cable bushings, neon tubing supports and ...
- A.5.2.1 General
- + A.5.2.2 Construction
- A.5.2.2.1 Cable bushings
- A.5.2.2.2 Neon tubing supports
- A.5.2.2.3 Cable supports
- + A.5.2.3 Tests
- A.5.2.3.1 General
- A.5.2.3.2 Polymeric neon tubing supports
- A.5.2.3.3 Polymeric cable supports
- + A.5.3 Through wall electrode receptacles
- A.5.3.1 General
- + A.5.3.2 Construction
- A.5.3.2.1 General
- A.5.3.2.2 Spacing
- + A.5.3.3 Tests
- A.5.3.3.1 General
- A.5.3.3.2 Temperature
- + A.5.4 Receptacle caps
- A.5.4.1 General
- A.5.4.2 Construction
- + A.5.4.3 Tests
- A.5.4.3.1 Test assembly
- A.5.4.3.2 Conditioning
- A.5.4.3.3 Rain test
- + A.5.5 Electrode receptacle enclosures
- A.5.5.1 Construction
- A.5.5.2 Tests
- + A.5.6 GTO cable splice enclosures
- A.5.6.1 General
- A.5.6.2 Construction
- A.5.6.3 Tests
- + A.5.7 Cold-cathode and over 1000V lampholder sy...
- A.5.7.1 General
- A.5.7.2 System construction
- A.5.7.3 Additional requirements for feed type l...
- A.5.7.4 Tests
- + A.5.8 Neon electrode splice and GTO cable polym...
- A.5.8.1 General
- A.5.8.2 Construction
- A.5.8.3 Tests
- + A.5.9 Neon electrode enclosure and GTO cable wi...
- A.5.9.1 General
- A.5.9.2 Construction
- A.5.9.3 Tests
- + A.6 Markings and instructions
- A.6.1 General
- + A.6.2 Electrode Receptacles
- A.6.2.1 Markings
- A.6.2.2 Installation instructions
- + A.6.3 Feed-type lampholders
- A.6.3.1 Markings
- + A.6.3.2 Installation instructions
- A.6.3.2.1 General
- + A.6.4 Interconnecting lampholders
- A.6.4.1 Markings
- A.6.4.2 Installation instructions
- + A.6.5 Polymeric neon electrode enclosures
- A.6.5.1 Markings
- A.6.5.2 Installation instructions
- + A.6.6 Through-wall electrode receptacles
- A.6.6.1 Markings
- A.6.6.2 Safety instructions
- A.6.6.3 Installation instructions
- + A.6.7 GTO cable splice enclosure
- A.6.7.1 Markings
- A.6.7.2 Installation instructions
- + A.6.8 GTO cable sleeves
- A.6.8.1 Markings
- A.6.8.2 Installation instructions
- + A.6.9 Electrode receptacle enclosures
- A.6.9.1 Markings
- + A.6.9.2 Installation instructions
- A.6.9.2.1 General
- A.6.9.2.2 Instructions for damp locations
- A.6.9.2.3 Instructions for wet locations
- A.6.9.2.4 Instructions for field installed pro...
- + A.6.10 Neon transformer enclosures
- A.6.10.1 Markings
- A.6.10.2 Installation instructions
- + A.6.11 Electrode receptacle insulators
- A.6.11.1 Markings
- A.6.11.2 Installation instructions
- + A.6.12 Receptacle caps
- A.6.12.1 Markings
- A.6.12.2 Installation instructions
- + A.6.13 Cable bushings, neon tubing supports and...
- A.6.13.1 Markings
- + A.6.13.2 Installation instructions
- A.6.13.2.1 Cable bushings
- A.6.13.2.2 Neon tubing supports
- A.6.13.2.3 Cable supports
- + A.6.14 Cold-cathode and over 1000V lampholder s...
- A.6.14.1 Markings
- A.6.14.2 Installation instructions
- + A.6.15 Neon electrode splice and GTO cable poly...
- A.6.15.1 Markings
- A.6.15.2 Installation instructions
- + A.6.16 Neon electrode enclosure and GTO cable w...
- A.6.16.1 Markings
- A.6.16.2 Suitable for dry or damp locations
- A.6.16.3 Suitable for wet locations
- A.6.16.4 Installation instructions
- + A.7 Tests
- A.7.1 Temperature test
- A.7.2 Dielectric voltage withstand test
- A.7.3 Resistance to moisture test
- A.7.4 Rain test
- A.7.5 Ground continuity
- A.7.6 Knockout test
- A.7.7 Thermal cycling
- A.7.8 Humidity conditioning
- + A.7.9 Inorganic materials tests
- A.7.9.1 Impact
- A.7.9.2 Environmental conditioning
- A.7.9.3 Thermal cycling
- A.7.10 Cold conditioning
- A.7.11 Ultraviolet radiation exposure
- A.7.12 Ozone exposure
- + A.7.13 Accelerated aging
- A.7.13.1 Wire, cable, GTO sleeves, and neon ele...
- A.7.13.2 Accelerated aging with thermal cycling...
- A.7.14 Strain relief
- + A.7.15 Retention test
- A.7.15.1 Neon electrode enclosure to neon tube ...
- A.7.15.2 Neon electrode enclosure to GTO sleevi...
- A.7.15.3 GTO cable with integral sleeve and str...
- + A.7.16 Tests for neon tubing supports and cable...
- A.7.16.1 Mounting means test
- A.7.16.2 High voltage wet location corona and a...
- + A.7.17 Neon electrode splice and GTO cable poly...
- + A.7.17.1 Electrostatic field test
- A.7.17.1.1 General
- A.7.17.1.2 Test samples
- A.7.17.1.3 Conditioning
- A.7.17.1.4 Dielectric
- A.7.17.2 Dielectric with steel shot
- A.7.17.3 Rain
- A.7.17.4 Conditioning
- + A.7.18 Ozone, ultraviolet radiation, heat and m...
- A.7.18.1 General
- + A.7.18.2 UV radiation generator
- A.7.18.2.1 Components
- A.7.18.2.2 Assembly
- + A.7.18.3 Ozone generator
- A.7.18.3.1 Components
- A.7.18.3.2 Assembly
- A.7.18.4 Test procedure
- + Annex B (normative)
- B.1 Scope
- B.2 Definitions
- + B.3 General
- B.3.1 Construction type designation
- + B.3.2 Installation type designation
- B.3.2.1 General
- B.3.2.2 Neon supplies intended for field and fa...
- B.3.2.3 Neon supplies for factory installation ...
- + B.4 Mechanical construction
- + B.4.1 General
- B.4.1.1 Neon supplies intended for dry location...
- B.4.1.2 Neon supplies intended for damp and wet...
- B.4.2 Metallic enclosures
- + B.4.3 Corrosion protection
- B.4.3.1 General
- B.4.3.2 Enclosures intended for wet locations
- + B.4.4 Polymeric enclosures
- B.4.4.1 General
- B.4.4.2 Type 1 Neon supplies
- B.4.4.3 Potting materials
- B.4.5 Gaskets and bushings
- + B.4.6 Accessibility barriers
- B.4.6.1 General
- B.4.6.2 Materials
- + B.4.7 Enclosure openings and open holes
- B.4.7.1 General
- + B.4.7.2 Openings for permanently connected supp...
- B.4.7.2.1 Openings for the connection of condu...
- B.4.7.2.2 Knockouts
- B.4.7.3 Openings for connection to Class 2 circ...
- B.4.7.4 Other open holes
- Table B.4.8
- Figure B.1
- + B.4.8 Securement of parts
- B.4.8.1 General
- B.4.8.2 Adhesives
- B.4.8.3 Thread-forming screws
- B.4.9 Sharp edges
- B.4.10 Mounting
- B.4.11 User-accessible controls
- + B.4.12 Equipment grounding and bonding
- B.4.12.1 General
- + B.4.12.2 Equipment grounding means
- B.4.12.2.1 General
- B.4.12.2.2 Grounding terminals
- B.4.12.2.2.1 General
- B.4.12.2.2.2 Pressure-wire terminals
- B.4.12.2.2.3 Wire-binding screws
- B.4.12.2.2.4 Wire-binding studs
- B.4.12.2.3 Grounding leads
- B.4.12.2.4 Grounding — Cord-connected neon sup...
- + B.4.12.3 Bonding
- B.4.12.3.1 General
- B.4.12.3.2 Polymeric materials
- B.4.12.3.3 Bonding leads
- B.4.12.3.4 Bonding for Type 4 neon supplies
- + B.4.13 Supply connections
- B.4.13.1 General
- B.4.13.2 Permanently connected supplies
- B.4.13.3 Supply terminals
- B.4.13.4 Supply leads
- + B.4.13.5 Cord- and plug-connected supplies
- B.4.13.5.1 General
- B.4.13.5.2 Strain and push-back relief
- B.4.13.5.3 Attachment plugs
- + B.4.13.6 Source of supply other than a branch c...
- B.4.13.6.1 General
- B.4.13.6.2 Class 2 power units
- + B.5 Electrical construction
- + B.5.1 Internal wiring
- B.5.1.1 General
- B.5.1.2 Prevention of wire damage
- B.5.2 Internal electrical connections (other th...
- + B.5.3 Output
- B.5.3.1 Output ratings
- B.5.3.2 Output terminals
- + B.5.3.3 Output cables
- B.5.3.3.1 General
- B.5.3.3.2 Output cables passing through metal
- B.5.3.3.3 Type 3 or Type 7 neon supplies
- B.5.3.3.4 Output return cable
- B.5.4 Input-to-output isolation
- + B.5.5 Electrical components
- B.5.5.1 General
- B.5.5.2 On/off switches
- + B.5.5.3 Overcurrent protection
- B.5.5.3.1 General
- B.5.5.3.2 Fuses
- + B.5.5.4 Capacitors
- B.5.5.4.1 General
- B.5.5.4.2 Pressure-interrupting-type oil-fille...
- B.5.5.5 Transformers
- B.5.5.6 Thermal protective devices
- B.5.5.7 Printed wiring boards
- B.5.5.8 Electrode receptacles
- + B.5.6 Secondary-circuit ground-fault protection...
- B.5.6.1 General
- B.5.6.2 Neon supplies not requiring secondary-c...
- B.5.6.3 Secondary-circuit ground-fault protecti...
- B.5.6.4 Isolated outputs
- B.5.6.5 Magnetically operated switches
- B.5.6.6 Service mode
- B.5.6.7 Reset of the output
- B.5.6.8 Secondary-circuit ground-fault protecti...
- + B.5.7 Spacings
- B.5.7.1 General
- + B.5.7.2 Spacing exceptions
- B.5.7.2.1 General
- B.5.7.2.2 Alternate spacing requirements
- B.5.7.2.3 Type 1 neon supplies
- B.5.7.2.4 Printed wiring boards with conformal...
- + B.5.8 Insulation
- B.5.8.1 General
- B.5.8.2 Insulation for Damp locations
- B.5.8.3 Insulation for Wet locations
- + B.6 Markings and instructions
- B.6.1 General
- + B.6.2 Identification
- B.6.2.1 General
- B.6.2.2 Neutral conductor
- B.6.2.3 Cold-Cathode lighting systems
- + B.6.3 Ratings
- B.6.3.1 Environmental location
- B.6.3.2 Orientation marking
- B.6.3.3 Maximum operating temperature
- B.6.3.4 Input
- B.6.3.5 Output
- + B.6.4 Cautionary markings
- B.6.4.1 General
- B.6.4.2 Replaceable fuses
- B.6.4.3 Secondary-circuit ground-fault protecti...
- B.6.4.4 Secondary-circuit ground-fault protecti...
- B.6.4.5 Neon supplies for vehicle use
- B.6.4.6 Cord-connected neon supplies
- B.6.4.7 Neon supplies for factory installation ...
- B.6.5 Installation Instructions
- + B.7 Tests
- + B.7.1 General
- B.7.1.1 Test procedure
- B.7.1.2 Source of supply for tests
- B.7.1.3 Electrodes and tubing used for testing
- Table B.7.1
- Table B.7.2
- B.7.2 Input measurement test
- B.7.3 Isolated output determination test
- + B.7.4 Output measurement test
- + B.7.4.1 Maximum output voltage
- B.7.4.1.1 General
- B.7.4.1.2 Maximum output voltage under open-ci...
- B.7.4.1.3 Maximum output voltage with capacita...
- B.7.4.1.4 Maximum output voltage with adjustab...
- Table B.7.3
- Table B.7.4
- + B.7.4.2 Maximum output current measurement
- B.7.4.2.1 General
- B.7.4.2.2 Measurement procedures
- B.7.4.2.3 Measurement conditions
- + B.7.5 Temperature test
- B.7.5.1 General
- B.7.5.2 Test enclosure
- B.7.5.3 Test oven
- + B.7.5.4 Temperature measurement
- B.7.5.4.1 Temperatures measured by thermocoupl...
- B.7.5.4.2 Coil and winding temperatures
- Figure B.6
- Table B.7.5
- Table B.7.6
- + B.7.6 Dielectric voltage-withstand tests
- B.7.6.1 General
- + B.7.6.2 Primary and secondary circuits
- B.7.6.2.1 General
- B.7.6.2.2 Isolated output neon transformers
- B.7.6.2.3 Neon transformers with a ground-refe...
- B.7.6.2.4 Neon power supplies
- B.7.6.2.5 Neon supplies with integral electrod...
- B.7.6.3 Barriers and insulating materials
- + B.7.7 Leakage current test
- B.7.7.1 General
- B.7.7.2 Primary-circuit filtering
- B.7.7.3 Leakage measurement
- + B.7.8 Input-to-output isolation test
- B.7.8.1 General
- + B.7.8.2 Neon supplies with feedback circuits
- B.7.8.2.1 General
- B.7.8.2.2 Abnormal
- B.7.8.2.3 Leakage current to ground
- B.7.9 Bonding circuit impedance test
- B.7.10 Strain and push-back relief test
- + B.7.11 Switch loading tests
- B.7.11.1 General
- B.7.11.2 Overload
- B.7.11.3 Endurance
- + B.7.12 Abnormal operation tests
- + B.7.12.1 Test conditions
- B.7.12.1.1 General
- B.7.12.1.2 Fuses
- B.7.12.1.3 Supply circuit
- B.7.12.1.4 Test duration and failure criteria
- B.7.12.1.5 Reset protector functions during te...
- B.7.12.2 Output open-circuit
- B.7.12.3 Abnormal component short- and open-cir...
- B.7.12.4 Output short-circuit abnormal temperat...
- B.7.12.5 Output shorted-to-ground abnormal test...
- + B.7.13 Mechanical tests
- B.7.13.1 Polymeric mounting means load
- B.7.13.2 Knockout
- + B.7.14 Wire-binding screw terminal tests
- B.7.14.1 Solid-wire tightening
- B.7.14.2 Performance verification of terminal a...
- + B.7.15 Secondary-circuit ground-fault parameter...
- B.7.15.1 General
- B.7.15.2 Neon supplies with a limited output
- + B.7.15.3 Ground-referenced midpoint neon suppl...
- B.7.15.3.1 General
- B.7.15.3.2 Test load
- B.7.15.3.3 User- or service-adjustable control...
- B.7.15.3.4 Test procedure
- Figure B.9
- Table B.7.15
- + B.7.15.4 Ground-referenced, end point return ne...
- B.7.15.4.1 General
- B.7.15.4.2 Test load
- B.7.15.4.3 User- or service-adjustable control...
- B.7.15.4.4 Test procedure
- + B.7.15.5 Isolated output midpoint return neon s...
- B.7.15.5.1 General
- B.7.15.5.2 Test load
- B.7.15.5.3 User- or service-adjustable control...
- B.7.15.5.4 Test procedure
- + B.7.15.6 Isolated output end point return neon ...
- B.7.15.6.1 General
- B.7.15.6.2 Test load
- B.7.15.6.3 User- or service-adjustable control...
- B.7.15.6.4 Test procedure
- + B.7.16 Secondary-circuit ground-fault protectio...
- + B.7.16.1 General
- B.7.16.1.1 Test conditions
- B.7.16.1.2 Circuit that limits or shuts off th...
- B.7.16.1.3 Test compliance
- + B.7.16.2 Component fault
- B.7.16.2.1 General
- B.7.16.2.2 Exceptions
- + B.7.16.3 Thermal aging
- B.7.16.3.1 General
- B.7.16.3.2 Elevated ambient conditioning
- B.7.16.3.3 Neon supplies provided with a therm...
- B.7.16.3.4 Additional conditioning
- B.7.16.4 Undervoltage and overvoltage
- B.7.16.5 Power supply interruption
- + B.7.16.6 Transient surge
- B.7.16.6.1 General
- B.7.16.6.2 Surge protective devices
- + B.7.16.7 Humidity
- B.7.16.7.1 General
- B.7.16.7.2 Test procedure
- Figure B.13
- Figure B.14
- + B.7.17 Damp and wet locations
- B.7.17.1 Damp locations
- + B.7.17.2 Wet locations
- + B.7.17.2.1 Accelerated aging of gaskets
- B.7.17.2.1.1 General
- B.7.17.2.1.2 Tensile strength and elongation
- B.7.17.2.1.3 Gasket assembly
- + B.7.17.2.2 Water spray
- B.7.17.2.2.1 General
- B.7.17.2.2.2 Apparatus
- B.7.17.2.2.3 Procedure
- + Annex C (normative)
- + C.1 Scope
- C.1.1
- C.1.2
- C.1.3
- C.1.4
- C.2 Definitions
- C.3 Components
- + C.4 Mechanical construction
- C.4.1 General
- C.4.2 Metal thickness
- C.4.3 Polymeric materials
- + C.4.4 Means of mounting and securement
- C.4.4.1 General
- C.4.4.2 Use of adhesives
- + C.5 Electrical construction
- C.5.1 General
- + C.5.2 Bonding
- C.5.2.1 General
- C.5.2.2 Bonding terminals
- C.5.3 Electrical connections
- + C.5.4 Lampholders
- C.5.4.1 Replacement lampholders
- C.5.4.2 Existing lampholders
- + C.6 Markings and instructions
- C.6.1 General
- + C.6.2 Markings applied to the LED kit or LED re...
- C.6.2.1 Identification markings
- C.6.2.2 Drilling or punching of openings
- + C.6.3 Field applied markings
- C.6.3.1 General
- C.6.3.2 Reuse of existing lampholders
- C.6.3.3 Replaceable lamps
- C.6.3.4 Tubular LED lamp retrofit kits
- + C.6.4 Instructions
- C.6.4.1 General
- C.6.4.2 LED kits for factory installation
- + C.6.4.3 LED retrofit kits for field installatio...
- C.6.4.3.1 General
- C.6.4.3.2 Retrofit kit electrical ratings
- C.6.4.3.3 Altering an enclosure of live parts
- C.6.4.3.4 Drilling or punching of openings
- C.6.4.3.5 Removing lampholders
- C.6.4.3.6 Installing new lampholders
- C.6.4.3.7 Reuse of existing lampholders
- C.6.4.3.8 Replaceable lamps
- C.6.4.3.9 Tubular LED lamp retrofit kits
- C.6.4.3.10 Environmental locations considerati...
- C.6.4.3.11 Installation instructions linked wi...
- + C.7 Tests
- C.7.1 LED retrofit kits
- C.7.2 LED kits for new signs
- + C.7.3 Installation test
- C.7.3.1 Retrofit kits
- C.7.3.2 LED kits
- + Annex D (normative)
- D.1 Special terminology
- + D.2 Construction
- D.2.1 Other than Class 2 circuits
- D.2.2 Class 2 circuits
- D.2.3 Coatings
- D.2.4 Direct support of live parts
- D.2.5 Spacings
- + D.3 Tests
- D.3.1 General
- + D.3.2 Printed wiring boards of neon power suppl...
- D.3.2.1 Dielectric voltage withstand with condi...
- D.3.2.2 Abnormal trace-to-trace short-circuit
- + D.3.3 Printed wiring boards within signs
- D.3.3.1 Flexing
- D.3.3.2 Dielectric
- D.3.3.3 Thermal conditioning
- D.3.3.4 Humidity conditioning
- D.3.3.5 Adhesion
- D.3.3.6 Insulation resistance test voltage
- D.3.3.7 Fault conditions
- + Annex E (informative)
- E.1 Dielectric voltage-withstand
- E.2 Grounding continuity
- E.3 Strain relief
- E.4 Polarity
- E.5 Ground screw torque
- E.6 Accessible edges
- E.7 Exclusion of water
- E.8 Test records
- + Annex F (informative)
- F.1 Component Standards
1.1
This Standard applies to electric signs, outline lighting, and display equipment for indoor or outdoor use, in nonhazardous locations, intended for installation in accordance with the Canadian Electrical Code, Part I wherein the sources of light are light emitting diodes (LED) or other electric lamp types including high voltage luminous-discharge types.
1.2
Electric signs using high voltage luminous-discharge-tubes are intended for installation on branch circuits of not more than
a) 750 V between conductors and involving lamp voltages of not more than 15 000 V for stationary signs; and
b) 125 V between conductors and involving lamp voltages of not more than 7500 V for portable signs.
c) 750 V between conductors and involving lamp voltages of more than 7500 V but not exceeding 15 000 V, not more than 7500 V to ground, and secondary current ratings not more than 30 mA, for portable and show-window luminous-discharge-tube signs and displays for indoor use.
1.3
Electric signs covered by this Standard include sectional signs, trailer-mounted signs, canopy signs, recessed signs, pole mounted signs, changing message signs, mechanically or electrically animated signs, and digital-display signs.
1.4
This Standard also applies to high voltage luminous-discharge-tube components (see Annex A), neon transformers and power supplies (see Annex B), and LED kits and LED retrofit kits for signs (see Annex C).
1.5
These requirements do not cover:
a) Luminaires, including those used for used for billboard illumination and other than advertising purposes (e.g., bathroom signage);
b) Portable luminaires;
c) Emergency lighting products;
d) Signs that do not use electricity;
e) The use of special-use lamps and LED arrays unless they are free of any photobiological hazards in accordance with CSA C22.2 No. 62471; and
f) Field-assembled signs approved in accordance with SPE-1000.
1.6
The values given in SI (metric) units are the standard. The values given in parentheses are for information only.
1.7
In this Standard, “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the standard; “should” is used to express a recommendation or that which is advised but not required; and “may” is used to express an option or that which is permissible within the limits of the standard.
Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material.
Notes to tables and figures are considered part of the table or figure and may be written as
requirements.
Annexes are designated normative (mandatory) or informative (nonmandatory) to define their application.
You may comment on any section of this document by clicking the “Submit Comment” link at the bottom of the relevant section.