Draft Details
- CSA C22.2 No. 144.1 - UL 943 Prelim Document.pdf (PDF document, 2 MB)
For PDF files, Adobe Acrobat Reader can be downloaded from the Adobe website.
1.1 This Standard applies to Class A, single- and three-phase, ground-fault circuit-interrupters intended for protection of personnel, for use only in grounded neutral systems in accordance with the NFPA 70®, National Electrical Code® (NEC®) and the Canadian Electrical Code, Part I, and Electrical Installations (Use), NOM-001-SEDE. These devices are intended for use on alternating current (AC) circuits of 120 V, 208Y/120 V, 120/240 V, 127 V, or 220Y/127 V, 60 Hz circuits.
NOTE: In Canada, the text “intended for protection of personnel” is excluded.
NFPA 70®, National Electrical Code®, and NEC® are registered trademarks of the National Fire Protection Association, Quincy, MA.
1.2 These requirements do not cover ground-fault circuit-interrupters intended for use in circuits served by a transformer having windings wholly insulated from each other.
1.3 This Standard applies to all Class A ground-fault circuit-interrupters. These Class A GFCIs are permitted to be integrated into other devices, in which case, besides complying with this Standard, these devices are to comply with the corresponding applicable Standard for the device in question.
1.4 This Standard includes minimum requirements for the function, construction, performance, and markings of ground-fault circuit-interrupters included in the scope.
1.5 This Standard is intended to cover only Class A GFCI devices.
1.6 This Standard also covers GFCIs of the self-contained type that are intended for installation in a counter, such as would be suitable for installation in a kitchen or bathroom countertop.
You may comment on any section of this document by clicking the “Submit Comment” link at the bottom of the relevant section.