- DRAFT STANDARD
- Legal Notice for Draft Standards
- Preface
- + 1 Scope
- + 1.1 General
- 1.1.1
- 1.1.2
- 1.2 Unitary equipment
- 1.3 Terminology
- 1.4 Units of measurement
- 2 Reference publications
- 3 Definitions
- 4 General requirements — Construction, design, ...
- + 5 Rating requirements
- + 5.1 General
- 5.1.1 Control settings
- 5.1.2 Standard ratings
- 5.1.3 Standard ratings for heating and cooling ...
- + 5.2 Performance ratings
- 5.2.1 Capacity ratings
- 5.2.2 Input ratings
- 5.2.3 Values of SCOP and ICOP
- 5.2.4 Application ratings
- + 5.2.5 Published ratings
- 5.2.5.1 Performance ratings
- 5.2.5.2 Application ratings
- 5.2.5.3 Capacity designation
- 5.2.5.4 Capacity ratings
- 6 Sampling plan
- 7 Performance requirements
- + 8 Tests
- + 8.1 General
- + 8.1.1 Tolerances
- 8.1.1.1
- 8.1.1.2
- 8.1.2 Test room requirements
- 8.1.3 Tested system installation
- 8.1.4 Settings for airflow through the indoor c...
- 8.1.5 Indoor coil inlet and outlet duct connect...
- 8.1.6 Indoor coil air property measurements and...
- 8.1.7 Airflow measuring apparatus
- 8.1.8 Electrical voltage supply and power measu...
- 8.1.9 Time measurements
- 8.1.10 Secondary capacity measurements
- 8.1.11 Measurement of test room ambient conditi...
- 8.1.12 Measurement of barometric pressure
- + 8.2 Tests and test conditions
- 8.2.1 General
- 8.2.2 Cooling tests
- 8.2.3 Heating tests
- 8.3 Secondary test methods
- 8.4 Tolerances
- + 9 Rating calculations
- 9.1 Cooling rated SCOPC calculations
- 9.2 Heating rated SCOPH calculations
- + Annex A (informative)
- A.1 Confidence limit
- A.2 Example — Sample size of two
- A.3 Example — Sample size of three
- + Annex B (normative)
- + B.1 Testing overview, conditions, and set-up
- + B.1.1 Test room requirements
- B.1.1.1 Test rooms
- B.1.1.2 Test room conditions
- B.1.1.3 Controller for the tested system
- B.1.1.4 Aligning indoor test room and system co...
- + B.1.2 Tested system installation requirements
- + B.1.2.1 General
- B.1.2.1.1 System installation
- B.1.2.1.2 Installation instructions
- B.1.2.1.3 Refrigerant lines
- + B.1.2.1.4 Refrigerant charging
- B.1.2.1.4.1 Instructions to use for charging
- B.1.2.1.4.2 Parameters to set and their target ...
- B.1.2.1.4.3 Charging tolerances
- B.1.2.1.4.4 Test to use for charging
- B.1.2.1.4.5 Heating only heat pumps
- B.1.2.1.4.6 Single-package systems
- B.1.2.2 Defrost control settings
- B.1.2.3 Requirements for a system having a mult...
- + B.1.3 Control settings for airflow through the ...
- B.1.3.1 Establishing control settings for testi...
- B.1.3.2 Cooling tests
- B.1.3.3 Heating tests
- + B.1.4 Indoor coil inlet and outlet duct connect...
- B.1.4.1 General
- + B.1.4.2 Outlet plenum for the indoor unit
- B.1.4.2.1 Standard indoor coils
- B.1.4.2.2 Multiple indoor coils or blowers
- B.1.4.2.3 Small-duct, high-velocity systems
- B.1.4.2.4 Test procedure
- B.1.4.3 Inlet plenum for the indoor unit
- + B.1.5 Indoor coil air property measurements and...
- + B.1.5.1 General
- B.1.5.1.1
- B.1.5.1.2
- B.1.5.1.3
- B.1.5.1.4
- B.1.5.2 Test set-up on the inlet side of the in...
- B.1.5.3 Indoor coil static pressure difference ...
- + B.1.5.4 Test set-up on the outlet side of the i...
- B.1.5.4.1 Test set-up
- B.1.5.4.2 Test procedure
- B.1.5.4.3 Outlet air damper box placement and r...
- B.1.5.4.4 Procedures to minimize temperature ma...
- B.1.5.4.5 Minimizing air leakage
- + B.1.5.5 Dry-bulb temperature measurement
- B.1.5.5.1
- B.1.5.5.2
- B.1.5.6 Water vapour content measurement
- B.1.5.7 Air damper box performance requirements...
- + B.1.6 Airflow measuring apparatus
- B.1.6.1 Construction
- B.1.6.2 Application
- B.1.7 Electrical voltage supply
- B.1.8 Time measurements
- + B.1.9 Test apparatus for the secondary space co...
- B.1.9.1 General
- + B.1.9.2 Outdoor air enthalpy method
- B.1.9.2.1 Measurements
- B.1.9.2.2 Apparatus
- B.1.9.3 Refrigerant enthalpy method
- + B.1.10 Measurement of test room ambient conditi...
- B.1.10.1 General
- B.1.10.2 Loop air enthalpy test method
- + B.1.10.3 Instrumentation set-up
- B.1.10.3.1 Air sampling geometry — Outdoor side...
- B.1.10.3.2 Maintaining uniformity of test room ...
- B.1.10.3.3 Air sampling tree size
- B.1.10.3.4 Connecting air sampling trees to an ...
- B.1.10.3.5 Measurement pairs
- B.1.10.3.6 Measurement of barometric pressure
- + B.1.10.4 Air sampling device and aspirating psy...
- B.1.10.4.1 Air sampling device requirements
- B.1.10.4.2 Aspirating psychrometer
- B.1.10.5 Measurements
- + B.2 Testing procedures
- + B.2.1 General requirements
- B.2.1.1 Overview
- B.2.1.2 Primary and secondary test methods
- B.2.1.3 Use of controls
- + B.2.1.4 Airflow through the outdoor coil
- B.2.1.4.1 Airflow measurements at the outdoor c...
- + B.2.1.4.2 Temperature requirements for air ente...
- B.2.1.4.2.1 Cooling mode tests
- B.2.1.4.2.2 Heating mode tests
- + B.2.1.5 Setting external static pressure condit...
- B.2.1.5.1 Test procedure
- + B.2.1.5.2 Cooling maximum air volume rate
- B.2.1.5.2.1 Cooling maximum air volume rate for...
- B.2.1.5.2.2 Cooling maximum air volume rate for...
- + B.2.1.5.3 Heating maximum air volume rate
- B.2.1.5.3.1 General
- B.2.1.5.3.1.1 Heating maximum air volume rate f...
- B.2.1.5.3.1.2 Setting external static pressure ...
- B.2.1.5.3.1.3 Multiple indoor blowers within a ...
- B.2.1.5.3.2 Non-ducted heat pumps
- B.2.1.6 Requirement for the air temperature dis...
- B.2.1.7 Requirement for the air temperature dis...
- B.2.1.8 Control settings of auxiliary resistive...
- B.2.1.9 Test sequence overview
- + B.2.2 Cooling mode tests
- + B.2.2.1 General
- B.2.2.1.1 External static pressure
- B.2.2.1.2 Capacity used to calculate cooling vi...
- B.2.2.1.3 Cooling learning test series
- B.2.2.1.4 Cooling rating test series
- B.2.2.1.5 Cooling rating test progression
- B.2.2.1.6 Cooling sensible virtual building loa...
- B.2.2.1.7 Cooling load simulation
- B.2.2.1.8 Cooling latent virtual building loads...
- B.2.2.1.9 Recording latent cooling performance
- + B.2.2.2 Cooling rating test procedures
- B.2.2.2.1 Before starting the cooling rating te...
- B.2.2.2.2 Conduct the cooling learning test ser...
- + B.2.2.2.3 Conduct the cooling rating tests
- B.2.2.2.3.1
- B.2.2.2.3.2
- B.2.2.2.3.3
- B.2.2.2.3.4
- B.2.2.2.3.5
- B.2.2.2.3.6
- B.2.2.2.3.7
- + B.2.3 Heating mode tests
- + B.2.3.1 General
- B.2.3.1.1 External static pressure
- B.2.3.1.2 Capacity used to calculate heating vi...
- B.2.3.1.3 Heating learning test series
- B.2.3.1.4 Heating rating test series
- B.2.3.1.5 Heating rating test progression
- B.2.3.1.6 Heating virtual building loads
- B.2.3.1.7 Heating load simulation
- B.2.3.2.1 Before starting the heating rating te...
- B.2.3.2.2 Conduct the heating learning test ser...
- + B.2.3.2.3 Conduct the heating rating tests
- B.2.3.2.3.1
- B.2.3.2.3.2
- B.2.3.2.3.3
- B.2.3.2.3.4
- B.2.3.2.3.5
- B.2.3.2.3.6
- B.2.3.2.3.7
- B.2.3.2.3.8
- + B.2.4 Additional requirements for the secondary...
- B.2.4.1 Required secondary capacity checks
- B.2.4.2 Operational mode for secondary capacity...
- B.2.4.3 Testing sequence for secondary capacity...
- B.2.5 Rounding of space conditioning capacities...
- + B.2.6 Laboratory testing to determine standby m...
- B.2.6.1 General
- + B.2.6.2 Standby power consumption
- B.2.6.2.1
- B.2.6.2.2
- B.2.6.2.3
- B.2.6.2.4
- B.2.6.2.5
- + B.2.6.3 Off-mode power consumption
- B.2.6.3.1
- B.2.6.3.2
- B.2.6.3.3
- B.2.6.3.4
- + B.2.6.4 Crankcase heater power consumption
- B.2.6.4.1 Ambient temperature-controlled crankc...
- B.2.6.4.2 System and controls configuration
- B.2.6.4.3 Test timing
- B.2.6.4.4 Test initiation
- B.2.6.4.5 Measuring crankcase heating power
- + B.2.6.4.6 Determining crankcase heating power
- B.2.6.4.6.1
- B.2.6.4.6.2
- B.2.6.4.7 Measuring P2X (T2CC)
- + B.2.6.4.8 Crankcase heater power calculation
- B.2.6.4.8.1
- B.2.6.4.8.2
- B.2.6.4.8.3
- B.2.6.4.8.4
- Table B.9
- Table B.10
- Table B.11
- + B.2.6.5 Drain pan heater power consumption
- + B.2.6.5.1 For drain pan heaters with single pow...
- B.2.6.5.1.1 System and controls configuration
- B.2.6.5.1.2 Test initiation
- B.2.6.5.1.3
- B.2.6.5.1.4
- + B.2.6.5.2 Drain pan heaters where power level v...
- B.2.6.5.2.1
- B.2.6.5.2.2 System and controls configuration
- B.2.6.5.2.3 Test initiation
- B.2.6.5.2.4
- B.2.6.5.2.5
- B.2.6.5.2.6
- B.2.6.5.2.7
- B.2.6.5.2.8
- + B.3 Calculations of performance values
- + B.3.1 Rated cooling performance
- B.3.1.1 Rated seasonal cooling COP
- B.3.1.2 Bin temperatures
- B.3.1.3 Instantaneous COP at 35 °C (95 °F) (ICO...
- + B.3.2 Rated heating performance
- B.3.2.1 Rated seasonal heating COP
- B.3.2.2 Bin temperatures
- B.3.2.3 Instantaneous COP at -15 °C (5 °F) (ICO...
- + Annex C (normative)
- + C.1 Calculation of cooling standby hours
- C.1.1 Cooling standby mode hours H3C
- C.1.2 Cooling off mode
- + C.1.3 Calculation of H2C
- C.1.3.1 General
- C.1.3.2 Calculation of H2C for a reversible hea...
- C.1.3.3 Calculation of H2C for an air condition...
- Table C.1
- Table C.2
- + C.2 Calculation of heating standby hours
- C.2.1 Heating standby mode
- C.2.2 Heating off mode
- C.2.3 Calculation of H2
- C.2.4 Calculation of H2 for a reversible heat p...
- C.2.5 Calculation of H2 for a heating-only heat...
- C.2.6 Calculation of H4
- + Annex D (informative)
- D.1 Introduction
- + D.2 Implementation process
- D.2.1 Variables and subscripts
- + D.2.2 Load-based testing implementation process...
- D.2.2.1 System rated parameters input
- D.2.2.2 Test mode, test type and test condition...
- + D.2.2.3 Load-based testing
- D.2.2.3.1 Virtual building model load and indoo...
- D.2.2.3.2
- D.2.2.3.3
- + D.2.2.3.4 Cooling
- D.2.2.3.3.1 Virtual building cooling load testi...
- D.2.2.3.3.2 Full-load cooling testing procedure...
- D.2.2.3.3.3 If irregular system behaviour preve...
- + D.2.2.3.5 Heating
- D.2.2.3.5.1 Virtual building heating load testi...
- D.2.2.3.5.2 Full-load testing and convergence
- D.2.2.3.5.3 If irregular system behaviour preve...
- Annex E (normative)
- + Annex F (normative)
- + F.1 General requirements
- F.1.1 Overview
- F.1.2 Application heating and cooling performan...
- + F.1.3 Determination of climate factors
- F.1.3.1
- F.1.3.2
- + F.1.4 Determination of equipment load
- + F.1.4.1
- F.1.4.1.1
- F.1.4.1.2
- F.1.4.2
- F.1.4.3
- + F.2 Fixed-capacity auxiliary heat
- F.2.1 General
- F.2.2 Capacity ratio
- F.2.3
- + F.2.4 Computation of RH(Tj) and application SCO...
- F.2.4.1
- F.2.4.2
- F.2.4.3
- F.2.4.4
- F.2.5 Non-electric central heating system
- + Annex G (normative)
- G.1 Overview
- + G.2 Hourly data sources
- G.2.1 General
- G.2.2 Canada normal weather
- G.2.3 U.S. normal weather
- + G.3 Heating and cooling bin hours
- + G.3.1 Heating bin hours
- G.3.1.1 Heating bin hours check for outdoor tem...
- + G.3.1.2 Heating bin hours within each bin
- G.3.1.2.1 General
- G.3.1.2.2 Daily heating degree days and “previo...
- G.3.1.2.3 Heating day
- G.3.1.3 Heating bin fractions for each bin
- + G.3.2 Cooling bin hours
- + G.3.2.1 Cooling bin hours for outdoor temperatu...
- G.3.2.1.1 General
- G.3.2.1.2 Exception 1
- G.3.2.1.3 Exception 2
- + G.3.2.2 Cooling bin hours within each bin
- G.3.2.2.1 General
- G.3.2.2.2 Daily cooling degree days and “previo...
- G.3.2.2.3 Cooling day
- G.3.2.3 Cooling bin fractions for each bin
- + G.4 Standby and off-mode hours
- G.4.1 Heating (and cooling) standby
- G.4.2 Off-mode
- + G.4.3 Determination of standby and off-mode bin...
- G.4.3.1 General
- G.4.3.2 Standby and off-mode bins
- G.4.3.3 Standby hours
- G.4.3.4 Heating standby, cooling standby, and o...
- G.5 Typical climate zone cities
- + Annex H (informative)
- + H.1 Power quality and electromagnetic compatibi...
- H.1.1 Power quality
- H.1.2 Who is responsible for power quality
- H.1.3 Heat-pump equipment impact
- + H.2 International equipment emission limit stan...
- H.2.1 General
- H.2.2 Harmonic emission limits and test procedu...
- H.2.3 Flicker emission limits and test procedur...
- H.2.4 Measurement
- + H.3 EMC-compliant equipment
- H.3.1 General
- H.3.2 European CE Marking
- + H.3.3 Emission testing and measurement for Cana...
- H.3.3.1 General
- H.3.3.2 Flicker emission testing and measuremen...
- + H.3.3.3 Harmonic emission testing and measureme...
- H.3.3.3.1 General
- H.3.3.3.2 Harmonic emission testing for complia...
- H.3.3.3.3 Harmonic emission testing for informa...
- H.3.3.3.4 Harmonic measurement requirements
- + Annex I (informative)
- I.1 Purpose
- I.2 Description
- Figure I.1
- Figure I.2
- I.3 Specifications
- Figure I.3
- Figure I.4
- Figure I.5
- Figure I.6
- Figure I.7
- Figure I.8
- Figure I.9
- I.4 Operation
- I.5 Future improvements
- + Annex J (informative)
- J.1 Purpose
- J.2 Description
- + J.3 Characterization of a test facility
- J.3.1 Test procedure
- J.3.2 Identifying transfer function coefficient...
- J.4 Feedforward compensation
- + Annex K (normative)
- K.1 Dual-fuel seasonal efficiency metric
- + K.2 Dual-fuel Utilization Efficiency
- K.2.1 Applicability
- K.2.2 Calculation
1.1 General
1.1.1
This Document applies to unitary air conditioners and heat pumps that are
a) factory-made;
b) air-source and air-sink;
c) single-split systems with matching assemblies or single package for use in ducted and/or non-ducted distribution systems;
d) intended for space-heating and/or air-conditioning applications in buildings;
e) electrically driven, mechanical, vapour-compression-type systems; and
f) rated below 19.0 kW (65 000 Btu/h) heating or cooling at standard rating conditions, in accordance with Clause 5.2.
1.1.2
This Document does not apply to the following:
a) water-to-air and/or water units; and
b) heat recovery.
1.2 Unitary equipment
Unitary equipment within the scope of this Document is outlined in Table 1.
1.3 Terminology
In this Document, “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with this Document; “should” is used to express a recommendation or that which is advised but not required; and “may” is used to express an option or that which is permissible within the limits of this Document.
Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material.
Notes to tables and figures are considered part of the table or figure and may be written as requirements.
Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.
1.4 Units of measurement
The values given in SI units are the units of record for the purposes of this Document. The values given in parentheses are for information and comparison only.
You may comment on any section of this document by clicking the “Submit Comment” link at the bottom of the relevant section.