Draft Details

Designation:CSA C22.2 NO. 60079-11
Source:CSA
Contact name:Simon Khavandi
Review start date:Nov 8, 2024
Review end date:Jan 7, 2025
Categories:Electrical
Contact email:mary.morgan(at)csagroup.org
Draft Scope/Description:

1DV DR Modification of Clause 1 to replace with the following:

 

This part of IEC 60079 standard specifies the construction and testing of intrinsically safe apparatus intended for use in explosive atmospheres, and for associated apparatus which is intended for connection to intrinsically safe circuits which enter such atmospheres.

 

This Type of Protection is applicable to electrical equipment in which the electrical circuits themselves are incapable of causing ignition of a surrounding explosive atmosphere. This includes electrical equipment which contains circuits that are intrinsically safe only under certain conditions, for example under battery supply with mains supply removed.

 

This document is also applicable to electrical equipment or parts of electrical equipment located outside the explosive atmosphere or protected by another Type of Protection listed in IEC 60079-0 UL 60079-0 and CSA C22.2 No. 60079-0, where the intrinsic safety of the electrical circuits in the explosive atmosphere may depend upon the design and construction of such electrical equipment or parts of such electrical equipment. The electrical circuits exposed to the explosive atmosphere are assessed for use in such atmospheres by applying this document.

 

This document applies to sensors connected to intrinsically safe circuits but does not apply to the protection of catalytic elements for Group IIC or Group IIB + H2.

 

This document does not apply to Ex Equipment cable glands.

 

The requirements for intrinsically safe systems are provided in IEC 60079-25 UL 60079-25 and CSA C22.2 No. 60079-25.

 

This document supplements and modifies the general requirements of IEC 60079-0, UL 60079-0 and CSA C22.2 No. 60079-0 except as indicated in Table 1. Where a requirement of this document conflicts with a requirement of IEC 60079-0 UL 60079-0 and CSA C22.2 No. 60079-0, the requirement of this document takes precedence.

 

Unless otherwise stated, the requirements in this document are applicable to both intrinsically safe apparatus and associated apparatus, and the generic term "apparatus" is used throughout the standard.

 

As this document applies only to electrical equipment, the term "equipment" used in the standard always means "electrical equipment".

 

This document applies to apparatus for use under the atmospheric conditions of IEC 60079-0 UL 60079-0 and CSA C22.2 No. 60079-0 with additional requirements for use at extended atmospheric pressures in the range from 60 kPa (0,6 bar), up to 110 kPa (1,1 bar).

 

Where references are made to other IEC standards, the referenced requirements found in these standards apply as modified by any applicable US National Differences for the standard (see Clause 2).

You may comment on any section of this document by clicking the “Submit Comment” link at the bottom of the relevant section.