- Emergency lighting equipment (New Edition)
- DRAFT STANDARD
- Legal Notice for Draft Standards
- Preface
- C22.2 No. 141-15
- + 1 Scope
- 1.1
- 1.2
- 1.3
- 1.4
- 2 Reference publications
- 3 Definitions
- + 4 General requirements
- 4.1 General
- + 4.2 Output rating
- 4.2.1 Unit equipment and emergency luminaires
- 4.2.2 Central power system
- 4.2.3 Rated discharged time
- + 4.3 Equipment performance
- 4.3.1 Criteria — Unit equipment and emergency l...
- 4.3.2 Criteria — Central power system
- + 4.3.3 Operating conditions
- 4.3.3.1
- 4.3.3.2
- 4.3.5 Compliance
- + 4.4 Indication of operating condition
- 4.4.1 Signal device
- 4.4.2 Signal device arrangement
- 4.4.3 Overload sensing circuit for central powe...
- 4.4.4 Central power system indicators (visual/a...
- 4.4.5 Phase failure
- 4.4.6 Equipment with auto-testing/auto-diagnost...
- + 4.5 Testing of operation of equipment with batt...
- 4.5.1
- 4.5.2
- 4.5.3
- + 5 Construction
- + 5.1 General
- 5.1.1
- 5.1.2
- 5.1.3
- 5.1.4
- 5.1.5
- 5.1.6
- 5.1.7
- 5.1.8
- 5.1.9
- 5.1.10
- 5.1.11
- + 5.2 Enclosures
- + 5.2.1 General
- 5.2.1.1
- 5.2.1.2
- 5.2.1.3
- 5.2.1.4
- 5.2.1.5
- 5.2.1.6
- 5.2.2 Nonmetallic materials
- 5.2.3 Thickness of sheet metal enclosures for l...
- 5.2.4 Thickness of cast enclosures for live par...
- + 5.2.5 Openings in enclosures
- 5.2.5.1
- 5.2.5.2
- 5.2.5.3 2
- 5.2.5.4 3
- 5.2.5.5 4
- 5.2.6 Doors and covers of enclosures
- + 5.3 Mechanical assembly
- 5.3.1
- 5.3.2
- 5.3.3
- + 5.4 Supply connections
- + 5.4.1 General
- 5.4.1.1
- 5.4.1.2
- + 5.4.2 Cord-connected equipment
- 5.4.2.1
- 5.4.2.2
- 5.4.2.3
- 5.4.2.4
- 5.4.2.5
- 5.4.2.6
- + 5.4.3 Equipment for permanent connection
- 5.4.3.1
- 5.4.3.2
- 5.4.3.3
- 5.4.3.4
- 5.4.3.5
- 5.4.3.6
- + 5.4.4 Strain relief
- 5.4.4.1
- 5.4.4.2
- 5.4.4.3
- 5.4.4.4
- 5.5 Bushings
- + 5.6 Current-carrying parts
- 5.6.1
- 5.6.2
- + 5.7 Wiring
- + 5.7.1 General
- 5.7.1.1
- 5.7.1.2
- 5.7.1.3
- 5.7.1.4
- 5.7.1.5
- 5.7.1.6
- + 5.7.2 Wiring materials
- 5.7.2.1
- 5.7.2.2
- + 5.7.3 Minimum conductor size
- 5.7.3.1
- 5.7.3.2
- 5.7.3.3
- + 5.8 Electrical insulation
- 5.8.1
- 5.8.2
- 5.8.3
- 5.8.4
- + 5.9 Storage batteries
- 5.9.1
- 5.9.2
- + 5.10 Charging means
- 5.10.1
- 5.10.2
- 5.10.3
- + 5.11 Output connections
- + 5.11.1 General
- 5.11.1.1
- 5.11.1.2
- 5.11.1.3
- 5.11.1.4
- 5.11.2 Overcurrent protection
- 5.11.3 Disconnecting means
- + 5.12 Fuses
- 5.12.1
- 5.12.2
- 5.12.3
- 5.13 Transformers
- + 5.14 Switches and controls
- 5.14.1
- 5.14.2
- + 5.15 Signal lights
- 5.15.1
- 5.15.2
- 5.15.3
- + 5.16 Spacings
- 5.16.1
- 5.16.2
- 5.16.3
- 5.16.4
- + 5.17 Separation of circuits
- 5.17.1
- 5.17.2
- 5.17.3
- + 5.18 BGrounding and bonding
- 5.18.1
- 5.18.2
- 5.19 Lamps
- + 5.20 Swivels
- 5.20.1
- 5.20.2
- 5.21 Risk of fire
- 5.22 21 Visibility requirements
- + 6 Marking
- 6.1
- 6.2
- 6.3
- 6.4
- 6.5
- 6.6
- 6.7
- 6.8
- 6.9
- 6.10
- 6.11
- 6.12
- 6.13
- 6.14
- 6.15
- 6.16
- 6.17
- 6.18
- 6.19
- + 7 Tests
- + 7.1 General
- 7.1.1
- 7.1.2
- 7.1.2
- 7.1.3
- 7.1.4
- + 7.2 Conditions for test
- 7.2.1
- 7.2.2
- 7.2.3
- 7.2.4
- 7.2.5
- 7.2.6
- + 7.3 Preparation of unit equipment
- 7.3.1
- 7.3.2
- + 7.4 Rating (input)
- 7.4.17.4.2
- 7.4.27.4.3
- 7.4.3 4
- 7.4.1
- The equipment maximum input current and power ...
- 7.4.2
- 7.4.3
- + 7.4.4
- 7.4.4
- 7.4.5
- + 7 x5 Charging means
- 7 x5.1
- 7 x5.2
- 7.5.3
- 7 x5.43
- + 7.5 6 Temperatures
- 7.56.1
- 7.56.2
- 7.56.3
- 7.56.4
- 7.6.5
- 7.56.5 6
- 7.7 y Over-voltage test (Extreme input voltage)...
- + 7.6 8 Leakage current
- 7.68.1
- 7.68.2
- 7.68.3
- 7.6.4
- 7.6.48
- 7.6.5
- 7.68.65
- 7.6.6
- 7.6.7
- 7.6.8
- 7.6.9
- + 7.7 9 Dielectric strength
- 7.79.1
- 7.9.2
- 7.9.2
- The test equipment shall employ a transformer ...
- 7.9.3
- 7.79.3
- 7.7
- 7
- + 7.8 10 Short-term recovery
- 7.810.1
- 7.810.2
- + 7.9 Charging means
- 7.9.1
- 7.9.2
- 7.9.3
- + 7.10 11 Cycling
- 7.1011.1
- 7.1011.2
- 7.1011.3
- + 7.11 12 Minimum ambient temperature
- 7.1112.1
- 7.1112.2 3
- + 7.12 13 Minimum extreme voltage
- 7.1213.1 General
- 7.1213.2 Requirements
- + 7.12.3 Central power system testing
- 7.12.3.1 Output frequency voltage and frequency...
- 7.12.3.2 Output load and power factor test
- 7.12.3.3 Battery discharge test
- 7.12.3.4 Overload testing
- 7.12.3.5 Phase failure
- 7.12.3.6 Central system indicator
- + 7.13 14 Electrolyte loss
- 7.1314.1
- 7.1314.2
- 7.1314.3
- + 7.14 15 Light output
- 7.15.1
- The test chamber shall have an interior ambien...
- 7.1415.21
- 7.1415.32
- 7.1415.43
- 7.1415.54
- 7.1415.65
- + 7.15 16 Lamp life
- 7.1516.1
- 7.1516.2
- 7.1516.3
- 7.17 Swivel test
- + 7.18 Lifting harnesses
- 7.18.1
- 7.18.2
- 7.19 Minimum light output for emergency lightin...
- 7.20 Energy performance and relevant markings f...
- 7.21 Component breakdown
- 7.232 Operation of equipment with auto-testing/...
- + 7.243 Central power system testing
- 7.243.1 Output voltage and frequency test
- 7.243.2 Output load and power factor test
- 7.243.3 Battery discharge test
- 7.243.4 Overload testing
- 7.243.5 Phase failure
- 7.243.6 Central system indicator
- + 8 Impedance networks
- + 8.1 Application
- 8.1.1
- 8.1.2
- 8.1.3
- + 8.2 General requirements
- 8.2.1 General
- 8.2.2 Low-voltage power-limited circuits
- + 8.3 Construction
- 8.3.1 Coupling capacitors
- 8.3.2 Electronic circuits
- + 8.3.3 High-frequency inverters
- 8.3.3.1
- 8.3.3.2
- 8.3.3.3
- + 8.4 Tests
- + 8.4.1 General
- 8.4.1.1
- 8.4.1.2
- + 8.4.2 Output voltage and current test
- 8.4.2.1
- 8.4.2.2
- 8.4.2.3
- 8.4.2.4
- 8.4.2.5
- 8.4.2.6
- + 8.4.3 Abnormal test
- 8.4.3.1
- 8.4.3.2
- 8.4.3.3
- 8.4.3.4
- 8.4.3.5
- 8.4.3.6
- + 8.4.4 Component breakdown test
- 8.4.4.1
- 8.4.4.2
- 8.4.4.3
- Table 4
- Table 5
- Table 6
- Table 7
- Table 87
- Figure 2
- + Annex A (normative)
- + A.1 General
- A.1.1
- A.1.2
- + A.2 General requirements
- A.2.1 General
- A.2.2 Illumination
- A.2.3 Diffuser flammability
- + A.3 Sign construction
- + A.3.1 Legends
- A.3.1.1 General
- A.3.1.2 Stroke width
- A.3.1.3 Aspect ratio of characters
- A.3.1.4 Bilingual legends
- A.3.1.5 Edge-lit signs
- + A.3.2 Directional indicators
- A.3.2.1 Size and shape
- A.3.2.2 Location
- A.3.2.3 Permanence
- A.3.3 Background
- + A.4 General test requirements
- A.4.1 Ambient conditions
- + A.4.2 Preparation for testing
- A.4.2.1 Lamp seasoning
- A.4.2.2 Lamp warm-up
- + A.4.3 Electrical supply characteristics
- A.4.3.1 AC power supply
- A.4.3.2 DC power supply
- + A.4.4 Instrumentation
- A.4.4.1 General
- A.4.4.2 Photometers
- A.4.4.2.1
- A.4.4.2.2
- A.4.4.2.3
- A.4.4.3 Electrical instruments
- + A.5 Luminance requirements
- + A.5.1 Exit signs in the non-energized state
- A.5.1.1 Test conditions
- A.5.1.2 Luminance uniformity within the legend
- A.5.1.3 Luminance uniformity across the backgro...
- A.5.1.4 Luminance contrast
- A.5.1.5 Luminance contrast of concealing mechan...
- + A.5.2 Exit signs using normal ac power
- A.5.2.1 Test conditions
- A.5.2.2 Luminance uniformity within legends and...
- A.5.2.2.1 Luminous legends and directional indi...
- A.5.2.2.2 Non-luminous legends and directional ...
- A.5.2.3 Luminance uniformity across the backgro...
- A.5.2.3.1 Luminous backgrounds
- A.5.2.3.2 Non-luminous backgrounds
- A.5.2.4 Luminance contrast
- A.5.2.5 Luminance contrast of concealing mechan...
- A.5.2.6 Minimum luminance of a luminous element...
- A.5.2.6.1
- A.5.2.6.2
- A.5.2.6.3
- + A.5.3 Exit signs using emergency dc power
- A.5.3.1 Test conditions
- A.5.3.2 Luminance uniformity within legends and...
- A.5.3.2.1 Luminous legends and directional indi...
- A.5.3.2.2 Non-luminous legends and directional ...
- A.5.3.3 Luminance uniformity across the backgro...
- A.5.3.3.1 Luminous backgrounds
- A.5.3.3.2 Non-luminous backgrounds
- A.5.3.4 Luminance contrast
- A.5.3.5 Luminance contrast of concealing mechan...
- A.5.3.6 Minimum luminance of a luminous element...
- A.5.3.6.1
- A.5.3.6.2
- A.5.3.6.3
- + A.6 Luminance measurements
- A.6.1 General
- + A.6.2 Illuminance apparatus
- A.6.2.1
- A.6.2.2
- + A.6.3 Luminous legend and directional indicator...
- A.6.3.1
- A.6.3.2
- A.6.3.3
- A.6.3.4
- + A.6.4 Background
- A.6.4.1
- A.6.4.2
- A.6.4.3
- A.6.4.4
- + A.7 Luminance calculations
- A.7.1 Contrast formula
- A.7.2 Mean luminance of the legend
- A.7.3 Mean luminance of the background
- + Figures
- Figure A.1
- Figure A.2
- Figure A.3
- + Figure A.4
- Figure A.5
- Figure A.6
- Figure A.7
- Figure A.8
- + Annex B (normative)
- + B.1 General
- B.1.1
- + B.2 General requirements
- B.2.1 General
- B.2.2 Illumination
- + B.2.3 Requirements for translucent pictogram le...
- B.2.3.1 Flammability requirements
- B.2.3.2 Mechanical rigidity
- + B.3 Sign construction
- B.3.1 General
- B.3.2 Legends
- B.3.3 Directional indicator
- B.3.4 Pictogram sign with additional elements
- + B.3.5 Colorimetric and photometric properties o...
- B.3.5.1 Conditions
- B.3.5.2 Colour requirements
- B.3.6 Permanence
- B.3.7 Flashing signs
- + B.4 General test requirements
- B.4.1 Test temperature conditions
- + B.4.2 Preparation for testing
- B.4.2.1 Lamp seasoning
- B.4.2.2 Lamp warm-up
- + B.4.3 Electrical supply characteristics
- B.4.3.1 AC power supply
- B.4.3.2 DC power supply
- + B.4.4 Instrumentation
- B.4.4.1 General
- B.4.4.2 Photometers
- B.4.4.2.1
- B.4.4.2.2
- B.4.4.2.3
- B.4.4.3 Electrical instruments
- + B.5 Luminance requirements
- + B.5.1 Exit signs using normal ac power
- B.5.1.1 Test conditions
- B.5.1.2 Luminance levels and uniformity within ...
- B.5.1.2.1
- B.5.1.2.2
- B.5.1.2.3
- B.5.1.3 Luminance uniformity within white colou...
- B.5.1.4 Luminance contrast ratio between white ...
- B.5.1.5 Flashing rate
- B.5.1.6 Flashing duty cycle
- + B.5.2 Exit signs using emergency dc power
- B.5.2.1 Test conditions
- B.5.2.2 Luminance
- + B.6 Measurement methodology
- B.6.1 General
- + B.6.2 Safety green colour and contrast white co...
- B.6.2.1
- B.6.2.2
- B.6.2.3
- B.6.2.4
- B.6.3 Flashing rate, light pulse duration, and ...
- Tables
- + Figures
- Figure B.2
- Figure B.3
- Figure B.4
- Figure B.5
- Figure B.6
- Figure B.7
- + Annex C (normative)
- + C.1 Construction
- C.1.1
- C.1.2
- C.1.3
- + C.2 Performance
- C.2.1
- C.2.2
- C.2.2 3
- C.2.3 4
- C.2.4 5
- C.2.6
- + Annex D (informative)
- D.1
- + Annex E (normative)
- + E.1 Diffuser — Flammability requirements
- E.1.1
- E.1.2
- E.1.3
- E.1.4
- + E.2 Exit signs with limited risk of fire and sh...
- E.2.1
- E.2.2
- + E.3 Thermal conditioning test
- E.3.1
- E.3.2
- E.3.3
- + Annex F (informative)
- F.1
1.1
This Standard applies to exit signs, unit equipment, emergency luminaires, and central power systems intended for connection to circuits with nominal voltages of 600 V and less and providing illumination in the event of a failure of the normal power supply for nonhazardous locations in accordance with the Rules of the Canadian Electrical Code, Part I.
1.2
This Standard includes requirements for the construction of emergency lighting equipment to preclude fire and shock hazards and to ensure that the equipment has the minimum capability for performing its intended function.
1.3
In this Standard, “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the standard; “should” is used to express a recommendation or that which is advised but not required; and “may” is used to express an option or that which is permissible within the limits of the Standard.
Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material.
Notes to tables and figures are considered part of the table or figure and may be written as requirements.
Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.
1.4
The values given in SI units are the units of record for the purposes of this Standard. The values given in parentheses are for information and comparison only.
You may comment on any section of this document by clicking the “Submit Comment” link at the bottom of the relevant section.