Draft Details

Designation:61000-3-3
Source:CSA
Review start date:Apr 29, 2020
Review end date:Jun 28, 2020
Categories:Electrical
Contact email:mary.morgan(at)csagroup.org
Associated materials (click link to download). You will need to be logged in to download any files:

Adobe Acrobat For PDF files, Adobe Acrobat Reader can be downloaded from the Adobe website.

Draft Scope/Description:

Scope:
This part of IEC 61000 is concerned with the limitation of voltage fluctuations and flicker impressed on the public low-voltage system. It specifies limits of voltage changes which may be produced by an equipment tested under specified conditions and gives guidance on methods of assessment. This part of IEC 61000 is applicable to electrical and electronic equipment having an input current equal to or less than 16 A per phase, intended to be connected to public low-voltage distribution systems of between 220 V and 250 V
line to neutral at 50 Hz, and not subject to conditional connection. Equipment which does not comply with
the limits of this part of IEC 61000 when tested with the reference impedance Zref of 6.4, and which
therefore cannot be declared compliant with this part, may be retested or evaluated to show conformity with IEC 61000-3-11. Part 3-11 is applicable to equipment with rated input current ≤ 75 A per phase and
subject to conditional connection. The tests according to this part are type tests. Particular test  conditions are given in Annex A and the test circuit is shown in Figure 1.

NOTE 1 The limits in this standard relate to the voltage changes experienced by consumers connected at the interface between the public supply low-voltage network and the equipment user’s installation. Consequently, if the actual impedance of the supply at the supply terminals of equipment connected within the equipment user’s installation exceeds the test impedance, it is possible that supply disturbance exceeding the limits could occur.

NOTE 2 The limits in this standard are based mainly on the subjective severity of flicker imposed on the light from 230 V 60 W coiled-coil filament lamps by fluctuations of the supply voltage. For systems with nominal voltage less than 220 V line to neutral and/or frequency of 60 Hz, the limits and reference circuit values are under consideration

You may comment on any section of this document by clicking the “Submit Comment” link at the bottom of the relevant section.