Main Categories

Categories: Energy
Contact: robert.reipas@csagroup.org
Origin: CSA
Close date: May 1, 2017
View moreView less
 

1 Scope

1.1 

This Standard defines requirements for the periodic inspection of balance of plant pressure retaining systems, components, and supports that form part of a CANDU nuclear power plant using a risk informed in-service inspection (RI-ISI) methodology. Periodic inspection (see Annex A for additional guidance) is considered to include the fluid boundary portions of balance of plant systems, components and piping, including their supports that comprise a complete nuclear power plant, excluding the following systems or portions thereof:

a) Systems, and systems connected thereto, containing the fluid that, under normal conditions, directly transports heat from nuclear fuel, and other systems whose failure can result in a significant release of radioactive substances.

Note: These systems or portions of systems are subject to inspection in accordance with Clause 3.3.1(a) in CSA N285.4.

 

b) Systems essential for the safe shutdown of the reactor and/or the safe cooling of the nuclear fuel in the event of a process system failure.

Note: These systems or portions of systems are subject to inspection in accordance with Clause 3.3.1(b) in CSA N285.4.

 

Compressors, turbines, generators, engines, and hydraulic or pneumatic cylinders are exempt from the inspection requirements of this Standard. This includes piping internal to equipment or mounted upon equipment that carries fluid from one chamber to another on the same foundation.

Note: To arrive at a periodic inspection program, the user should consider the inspections, examinations, and tests performed by other programs such as pipe wall thinning, vessel inspections, equipment reliability, and maintenance programs in addition to RI-ISI. Inspections performed as part of supporting programs are not expected to be repeated in this periodic inspection program, but should be credited to this periodic inspection program to provide assurance that the program satisfies the intended purpose as described in Annex A.

1.2 

This Standard addresses the following requirements

a) failure aspects;

b) classification of areas subject to inspection;

c) provision for access;

d) inspection techniques and procedures;

e) personnel qualifications;

f) frequency of inspection;

g) responsibilities;

h) documentation;

i) records;

j) evaluation of inspection results;

k) dispositioning; and

l) repair, replacement and modification requirements.

1.3 

The values given in SI units are the units of record for the purposes of this Standard. The values given in parentheses are for information and comparison only.

1.4 

In this Standard, “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the standard; “should” is used to express a recommendation or that which is advised but not required; and “may” is used to express an option or that which is permissible within the limits of the standard.

Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material.

Notes to tables and figures are considered part of the table or figure and may be written as requirements.

Annexes are designated normative (mandatory) or informative (nonmandatory) to define their application.

Categories: Energy
Contact: robert.reipas@csagroup.org
Origin: CSA
Close date: May 2, 2017
View moreView less
 

This is a proposed amendment to N293-12 - Fire protection for nuclear power plants

Categories: Energy
Contact: tony.wong@csagroup.org
Origin: CSA
Close date: May 2, 2017
View moreView less
 

1. Scope

1.1

This Standard applies only to electrically driven, mechanical, vapour-compression-type systems.

Large air conditioners and heat pumps rated above 19 kW (65 000 Btu/h) cooling or heating capacity at standard rating conditions for both single- and three-phase electrical power supplies

 All sizes of single packaged vertical air conditioners and heat pumps and air-conditioning condensing units.

 

Note: See Tables1 to 3 for classifications of air conditioners, heat pumps, and air-conditioning condensing units.

 

1.2

In CSA Standards, “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the standard; “should” is used to express a recommendation or that which is advised but not required; “may” is used to express an option or that which is permissible within the limits of the standard; and “can” is used to express possibility or capability. Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material. Notes to tables and figures are considered part of the table or figure and may be written as requirements. Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application

1.3

The values given in SI (metric) units are the standard. The values given in parentheses are for information only.

Contact: leila.julazadeh@csagroup.org
Origin: CSA
Close date: May 6, 2017
View moreView less
 

Scope

1.1
This Standard provides criteria for the structural design and appraisal of structures or structural elements made from wood or wood products, including graded lumber, glued-laminated timber, unsanded plywood, oriented strandboard (OSB), composite building components, shearwalls and diaphragms, timber piling, pole-type construction, prefabricated wood I-joists, structural composite lumber products, preserved wood foundations, and their structural connections. This Standard employs the limit states design method. 

1.2
In CSA Standards, "shall" is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the standard; "should" is used to express a recommendation or that which is advised but not required; "may" is used to express an option or that which is permissible within the limits of the standard. 

Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material. 

Notes to tables and figures are considered part of the table or figure and may be written as requirements. 

Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.

Contact: ken.phu@csagroup.org
Origin: CSA
Close date: May 7, 2017
View moreView less
 

This Standard covers polymeric subsurface stormwater management structures and accessories used in the collection, detention, retention, and infiltration of stormwater runoff. Applications include, but are not limited to, commercial, municipal, residential, agricultural, industrial, recreational, and highway drainage.

Categories: Energy
Contact: lorraine.mccourt@csagroup.org
Origin:
Close date: May 15, 2017
View moreView less
 

1 Scope

1.1 

This Standard applies to newly produced outdoor cooking gas appliances (see Clause 3) constructed entirely of new, unused parts and materials. Outdoor cooking gas appliances submitted for examination under this Standard are classified as portable, stationary, or built-in.

1.2 

This Standard applies to outdoor cooking gas appliances mounted to the exterior of a recreational vehicle (RV grills) (see Clause 3) for connection to the recreational vehicle's low pressure LP gas supply system (see Clause 1.8). It does not apply to outdoor cooking gas appliances for installation in the interior living space of a recreational vehicle.

1.3 

This Standard does not apply to outdoor cooking gas appliances for installation in or on boats.

1.4 

An outdoor cooking gas appliance may be a:

a) broiler unit;

b) top or surface unit;

c) oven;

d) combination of (a), (b) or (c) above, or any other outdoor cooking gas appliance; or

e) RV grill.

1.5 

Ovens shall not be of the self-cleaning type (see Clause 3).

1.6 

Outdoor cooking gas appliances may be for connection to:

a) a fixed fuel piping system.

b) a remote self-contained liquefied petroleum gas supply system (see Clause 3, Definitions), provided the appliance is supplied with remote mounting and retention means for the attachment of a single cylinder with a maximum size in accordance with Clause 1.6(b) or Clause 4.4.4(c) and instructions for installing the mounting and retention means within the built-in enclosure.

c) a self-contained liquefied petroleum gas supply system with an integral cylinder mounting means, for attachment to a single cylinder:

i) outdoor cooking gas appliances with input ratings less than 80,000 Btu/h shall be designed to accommodate a vertically mounted cylinder with a maximum size of 20 lb (9.1kg) of fuel.

ii) outdoor cooking gas appliances with input rating greater than or equal to 80,000 Btu/h shall be designed to accommodate a vertically mounted cylinder with a maximum size of 30 lb (13.6 kg) of fuel.

 

d) a self-contained liquefied petroleum gas supply system with an integral cylinder mounting means for the attachment of not more than two vertically mounted vapor withdrawal cylinders, each with a maximum size of 20 lb (9.1 kg) of fuel for outdoor cooking gas appliances with input ratings greater than or equal to 80,000 Btu/hr.

1.7 

This Standard applies to outdoor cooking gas appliances operating at inlet gas pressures not to exceed 1/2 psi (3.5 kPa) for connection to a fixed fuel piping system for use with:

a) natural gas;

b) manufactured gas;

c) mixed gas;

d) liquefied petroleum gases; and

e) LP gas-air mixtures.

This Standard also applies to outdoor cooking gas appliances designed for connection to self-contained LP gas supply systems (see Clause 4.5) operating at regulated outlet pressures:

a) not to exceed 11 in wc (2.74 kPa); and

b) in excess of 11 in wc (2.74 kPa) but not greater than 5 psi (34.5 kPa).

The construction of outdoor cooking gas appliances for use with the above-mentioned gases is covered under Clause 4, Construction.

The performance of outdoor cooking gas appliances for use with the above-mentioned gases is covered under Clause 5, Performance.

1.8 

Built-in outdoor cooking gas appliances may be for connection to:

a) a fixed fuel piping system; or

b) a remote self-contained liquefied petroleum gas supply system (see Clause 3, Definitions), provided the appliance is supplied with remote mounting and retention means for the attachment of a single cylinder with a maximum size in accordance with Clause 1.6(b) and instructions for installing the mounting and retention means within the built-in enclosure.

1.9 

An outdoor cooking gas appliance conforming to Clause 1.6(c)(ii), and that is capable of accepting either a 20 lb (9.1 kg) or a 30 lb (13.6 kg) LP gas cylinder, shall have all applicable tests in Clause 4 and Clause 5 conducted with both size cylinders.

1.10 

An outdoor cooking gas appliance having integral mounting and retention means shall be designed so a spare 20 lb (9.1 kg) or 30 lb (13.6kg) LP gas cylinder cannot be stored within any enclosure, or under the firebox of the appliance.

1.11 

Throughout this document gage pressures are designated in pounds per square inch, (psi) and kilopascals (kPa). Use of the terminology “psig” is not used. Where “psi” is used it is understood to be pound per square inch gage. Absolute pressures are not used in this Standard.

1.12 

This Standard contains SI (Metric) equivalents to the yard/pound quantities, the purpose being to allow the Standard to be used in SI (Metric) units. (IEEE/ASTM SI 10, American National Standard for Metric Practice, or ISO 80000-1:2009, Quantities and units – Part 1: General (Standard for use of the International System of Units (SI): The Modern Metric System, IEEE/ASTM SI 10 or ISO 80000-1:2009 Quantities and units - Part 1: General are is used as a guide in making metric conversion from yard/pound quantities.) If a value for a measurement and a corresponding value in other units are stated, the first stated value is to be regarded as the requirement. The given corresponding value may be approximate. If a value for a measurement and a corresponding value in other units are both specified as a quoted marking requirement, the first stated unit, or both shall are to be provided.

1.13 

In this Standard, “shall” is used to express a requirement, i.e., a provision that the user shall satisfy in order to comply with the standard; “should” is used to express a recommendation or that which is advised but not required; and “may” is used to express an option or that which is permissible within the limits of the standard.

Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material.

Notes to tables and figures are considered part of the table or figure and may be written as requirements.

Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.

1.14 

Clause 7 contains provisions that are unique to the United States.

1.15 

Clause 8 contains provisions that are unique to Canada.

1.16 

Clause 2 contains a list of standards specifically referenced in this Standard and sources from which these reference standards may be obtained.

1.17 

An outdoor cooking gas appliance covered by this Standard need not comply with the provisions of the Standard for Gas-Fired Appliances for Outdoor Installations, CAN1-2.21.

Contact: tim.pope@csagroup.org
Origin: CSA
Close date: May 16, 2017
View moreView less
 

Draft Amendment to C22.1

Contact: tara.leitan@csagroup.org
Origin: CSA
Close date: May 18, 2017
View moreView less
 
Contact: ana-maria.tomlinson@csagroup.org
Origin: CSA
Close date: May 23, 2017
View moreView less
 

Scope

1.1

This standard covers asphalt core boards intended for use as a substrate to receive an asphalt-based, low-slope roof membrane system (built-up or modified-bitumen).  In such systems, the roofing membrane may be adhered with hot asphalt or cold-applied adhesive or heat welded to asphalt core board or mechanically attached through asphalt core board to the structural deck. This standard applies to asphalt core boards installed horizontally and vertically (on flashings and parapets). 

1.2

This standard does not specify requirements for the use of asphalt core board in protecting a substrate.

This standard does not address asphalt based protection boards used in waterproofing; for information on these products, refer to ASTM Standard Specification D6506.

Asphalt core boards addressed in this standard are not intended as substrates for vertical flashings unless fully supported, in a low-slope roofing system.

1.3

The values given in SI (metric) units are the standard.  The values given in parentheses are for information only.

 

Categories: Energy
Contact: tony.wong@csagroup.org
Origin: CSA
Close date: May 23, 2017
View moreView less
 

1 Scope

1.1

This Standard applies to factory-manufactured residential, commercial, and industrial packaged terminal air-conditioners and heat pumps as defined in Clause 3.

1.2

This Standard applies to electrically operated vapour-compression refrigeration systems.

1.3

Packaged terminal air-conditioners and heat pumps are intended for unducted installation, but may be employed with ductwork having external static resistance up to 25 Pa (0.1 in H2O).

1.4

This Standard does not apply to the following:

a) heat-operated air-conditioning/heat pump equipment or room air-conditioners/heat pumps, as defined in CAN/CSA-C368.1;

b) water-to-air and brine-to-air heat pumps, as defined in CAN/CSA-C13256-1 and ISO 13256-1;

c) unitary air-conditioners and air-source unitary heat pumps, as defined in CAN/CSA-C656 and ANSI/AHRI 210/240, with capacities less than 19 000 W (65 000 Btu/h);

d) commercial and industrial unitary air-conditioners and heat pumps, as defined in CAN/CSA-C746 and ANSI/AHRI 340/360, with capacities of 19 000 W (65 000 Btu/h) or greater;

e) commercial and industrial single package vertical air-conditioners and heat pumps, as defined in ANSI/AHRI 390, with capacities of 39 300 W (134 000 Btu/h) or less; and

f) units with integral gas-fired heating.

1.5

In this Standard, “shall” is used to express a requirement, i.e., a provision that the user is obliged to satisfy in order to comply with the standard; “should” is used to express a recommendation or that 

which is advised but not required; and “may” is used to express an option or that which is permissible within the limits of the standard.

Notes accompanying clauses do not include requirements or alternative requirements; the purpose of a note accompanying a clause is to separate from the text explanatory or informative material.

Notes to tables and figures are considered part of the table or figure and may be written as requirements.

Annexes are designated normative (mandatory) or informative (non-mandatory) to define their application.

1.6

The values given in SI units are the units of record for the purposes of this Standard. The values given in parentheses are for information and comparison only.

Categories: Electrical
Contact: allan.hawley@csagroup.org
Origin: CSA
Close date: May 23, 2017
View moreView less
 

2 Scope
2.1 Applicable to Class I and II, Division 2 and Class III, Divisions 1 and 2
locations
2.1.1 This standard applies only to equipment, circuits, and components for use in Class I and II, Division 2 and Class III, Divisions 1 and 2 hazardous (classified) locations as defined in the National Electrical Code® (NEC®) ANSI/NFPA 70 or in the Canadian Electrical Code (CEC) CSA C22.1.
NOTE 1 Some equipment designed for use in unclassified locations is permitted by the NEC® or CEC for installation in Division 2 locations. The judgment of acceptability for the installation would be determined by the authority having jurisdiction. Such equipment would not have the hazardous location marking or documentation described in this standard. It is anticipated that such equipment would comply with the other requirements in this standard and that the determination of compliance is elementary
(e.g., a nonarcing instrument inside a Type 4 or Type 12 enclosure used in a Class II, Division 2 location).
NOTE 2 Throughout this standard, reference to CAN/CSA C22.2 No. 60079-0 and UL 60079-0 are made as CSA/UL 60079-0. Similarly reference to CAN/CSA C22.2 No.60079-1 and UL 60079-1 are made as CSA/UL 60079-1. Similarly reference to CAN/CSA C22.2 No. 60079-11 and UL 60079-11 are made as CSA/UL 60079-11.
Similarly reference to CAN/CSA C22.2 No. 60079-15 and UL 60079-15 are made as CSA/UL 60079-15.
FOR PUBLIC REVIEW, DO NOT DISTRIBUTE
NOTE 3 The US and Canadian adoptions of IEC 60079-0, IEC 60079-1, IEC 60079-11 and IEC 60079-15 may be adopted at different revision levels and may have different National Deviations.
2.2 Applicable to associated nonincendive field wiring apparatus
2.2.1 This standard also applies to associated nonincendive field wiring apparatus located in a non-hazardous (unclassified) location specifically designed to directly connect to nonincendive field wiring in Class I and II, Division 2 and Class III, Divisions 1 and 2 hazardous (classified) locations.
NOTE The 2015 CEC does not address nonincendive field wiring circuits in Class II or Class III hazardous locations.
2.3 Applicable ambient conditions
2.3.1 The requirements of this standard are based on consideration of the following ambient conditions:
a) A lower ambient temperature of -50°C or higher.
b) An upper ambient temperature of 40 °C or lower.
c) An oxygen concentration of not greater than 21 percent by volume.
d) A pressure of 80 kPa (0.8 bar) to 110 kPa (1.1 bar).
NOTE Equipment specified for atmospheric conditions beyond the above limits may be subject to additional investigation.
2.4 Not applicable to specified ignition mechanisms
2.4.1 This standard is not applicable to mechanisms of ignition from external sources, such as static electricity or lightning, that are not related to the electrical characteristics of the equipment.
FOR PUBLIC REVIEW, DO NOT DISTRIBUTE
2.5 Not applicable to specific products
2.5.1 This standard does not apply to electric luminaires for use in Division 2 hazardous (classified) locations.
2.5.2 This standard does not apply to electric motors, electric heaters, heat tracing cables, and similar heat-producing products, except where they are an integral part of the equipment under evaluation, for use in Division 2 locations. Where electric motors, electric heaters, heat tracing cables or similar heat-producing products are an integral part of the equipment under evaluation, applicable requirements from the Division 2 hazardous locations standards for these products shall be considered.
2.5.3 In the United States, this standard does not apply to battery-operated flashlights and lanterns within the scope of UL 783.

Contact: cathryn.cortissoz@csagroup.org
Origin: CSA
Close date: May 28, 2017
View moreView less
 

This standard specifies requirements for an organizational program for worker-carers providing care to adult care recipients (e.g., adults with disabilities, elderly dependents).

Contact: cathryn.cortissoz@csagroup.org
Origin: ISO
Close date: May 28, 2017
View moreView less
 

This is an adoption without deviation of the identically titled ISO standard. This standard is available for viewing by request. 

Contact: cathryn.cortissoz@csagroup.org
Origin: ISO
Close date: May 28, 2017
View moreView less
 

This is an adoption without deviation of the identically titled ISO standard.

Contact: cathryn.cortissoz@csagroup.org
Origin: ISO
Close date: May 28, 2017
View moreView less
 

This is an adoption without deviation of the identically titled ISO standard.

Contact: cathryn.cortissoz@csagroup.org
Origin: ISO
Close date: May 28, 2017
View moreView less
 

This is an adoption without deviation of the identically titled ISO Standard.

Contact: cathryn.cortissoz@csagroup.org
Origin: ISO
Close date: May 28, 2017
View moreView less
 

This is an adoption without deviation of the identically titled ISO Standard.

Contact: cathryn.cortissoz@csagroup.org
Origin: ISO
Close date: May 28, 2017
View moreView less
 

This is an adoption without deviation of the identically titled ISO Standard.

Contact: cathryn.cortissoz@csagroup.org
Origin: ISO
Close date: May 28, 2017
View moreView less
 

This is an adoption without deviation of the identically titled ISO Standard.

Contact: cathryn.cortissoz@csagroup.org
Origin: ISO
Close date: May 28, 2017
View moreView less
 

This is an adoption without deviation of the identically titled ISO Standard.